Table 22 - Electrical data - TKD/TKH Compressor motor and condenser motor
(1) At Eurovent rating conditions : Indoor return Air (27°C DB / 19°C WB) - Ambiant 35°C
(2) per motor
Table 23 - Electrical data - YKD/YKH Compressor motor and condenser motor
(1) At Eurovent rating conditions : Indoor return Air (27°C DB / 19°C WB) - Ambiant 35°C
(2) per motor
TKD/H TKD/H TKD/H TKD/H
155 175 200 250
Compressor
Number 2 2 2 2
Type Scroll Scroll Scroll Scroll
Model 9T / 5T 10T / 6.7T 9T / 9T 10T / 10T
Rated Amps (1) (A) 15.0 / 8.5 15.1 / 11.4 14.7 / 14.7 15.3 / 15.3
Locked rotor Amps (2) (A) 118 / 65.5 118 / 101 118 / 118 118 / 118
Outdoor Fan
Nominal Airflow (m
3
/h) 15350 19750 21000 23500
Type Axial Axial Axial Axial
Diameter (mm) 660 660 710 710
Drive type Direct Direct Direct Direct
Number 2 2 2 2
Motor HP (kW) 0.25 0.25 0.56 0.56
Motor Rated Amps (1) (A) 1.6 1.6 2.3 2.3
Motor Locked rotor Amps (2) (A) 3.8 3.8 5.8 5.8
Motor RPM (rpm) 925 925 925 925
YKD/H YKD/H YKD/H YKD/H
155 175 200 250
Compressor
Number 2 2 2 2
Type Scroll Scroll Scroll Scroll
Model 9T / 5T 10T / 6.7T 9T / 9T 10T / 10T
Nominal Amps (1) (A) 15.0 / 8.5 15.1 / 11.4 14.7 / 14.7 15.3 / 15.3
Locked rotor Amps (2) (A) 118 / 65.5 118 / 101 118 / 118 118 / 118
Outdoor Fan
Nominal Airflow (m
3
/h) 15350 19750 21000 23500
Type Axial Axial Axial Axial
Diameter (mm) 660 660 710 710
Drive type Direct Direct Direct Direct
Number / Voltage 2 2 2 2
Motor HP (kW) 0.25 0.25 0.56 0.56
Motor Rated Amps (1) (A) 1.6 1.6 2.3 2.3
Motor Locked rotor Amps (2) (A) 3.8 3.8 5.8 5.8
Motor RPM (rpm) 925 925 925 925