Trane RT-SVX19A-E4 Thermostat User Manual


 
Installation
29RT-SVX19A-E4
Table 24 - Electrical data - WKD/WKH Compressor motor and condenser motor
(1) At Eurovent rating conditions : Indoor return Air (27°C DB / 19°C WB) - Ambiant 35°C
(2) per motor
Table 25 - Electrical data - TKD/TKH Supply fan motor
(4) At the nominal airflow with standard drive
(5) At the nominal airflow with oversized drive when available
YKD/H YKD/H YKD/H YKD/H
155 175 200 250
Indoor Fan
Nominal Airflow (m
3
/h) 8500 9850 11210 14100
Static pressure available (4) (Pa) 150 75 175 75
Maximum static pressure available (5) (Pa) 350 375 450 375
Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
Diameter / Width (in / in) 15" / 15" 15" / 15" 18" / 18" 18" / 18"
Drive type Belt Belt Belt Belt
Number # 1 1 1 1
Motor HP (Standard/Oversized) (kW) 2.2 / 3.0 3.0 / 4.6 3.0 / 4.6 4.6 / -
Motor Rated Amps (Standard/Oversized) (A) 4.6 / 6.5 6.5 / 9.0 6.5 / 9.0 9 / -
Motor Locked rotor Amps (Standard/Oversized) (A) 36.4 / 57 57 / 71.9 57 / 71.9 71.9 / -
Motor RPM (Standard/Oversized) (rpm) 1450 / 2870 2870 / 2900 2870 / 2900 2900 / -
WKD/H WKD/H WKD/H
125 155 200
Compressor
Number 2 2 2
Type Scroll Scroll Scroll
Model 6T / 6T 7.5T /7.5T 10T / 10T
Rated Amps (1) (A) 10.0 / 10.0 12.1 / 12.1 17.5 / 17.5
Locked rotor Amps (2) (A) 74 / 74 79 / 79 98 / 98
Outdoor Fan
Nominal Airflow (m
3
/h) 15300 15850 23600
Type Axial Axial Axial
Diameter (mm) 660 660 710
Drive type Direct Direct Direct
Number 2 2 2
Motor HP (kW) 0.25 0.25 0.56
Motor Rated Amps (1) (A) 1. 6 1. 6 2.3
Motor Locked rotor Amps (2) (A) 3.8 3.8 5.8
Motor RPM (rpm) 925 925 950