Trane RT-SVX19A-E4 Thermostat User Manual


 
Installation
17RT-SVX19A-E4
Component air pressure drops
Table 7 - YKD/YKH Pressure drop through accessories
Filter Filter Economizer Economizer
Airflow EU2/G2 EU4/G4
100%
outside air
100%
return air
YKD/YKH 155
6800 13 27 8 6
7650 16 30 10 7
8500 19 34 12 8
9350 22 37 14 9
10200 26 40 16 10
YKD/YKH 175
7870 17 30 10 7
8860 21 34 12 8
9850 25 38 15 9
10840 30 43 17 11
11830 35 47 20 12
YKD 200
8970 12 26 29 6
10090 15 30 37 8
112 10 19 33 45 9
12330 23 37 55 11
13450 27 41 65 13
YKH 200
8970 11 23 33 6
10090 14 26 41 8
112 10 17 29 51 9
12330 20 33 61 11
13450 23 36 72 13
YKD 250
11280 18 32 46 10
12690 24 36 58 12
14100 29 41 71 14
15510 36 46 86 17
16920 43 51 102 19
YKH 250
11280 17 30 52 10
12690 21 34 65 12
14100 26 38 80 14
15510 31 43 96 17
16920 36 47 114 19