– 65 –
No.
6
Item
Air speed
selection
(Continued):
In case of
Slim Duct Type
Outline of specifications
Slim Duct Type
Item code
[5d]
SW501 (1)/(2)
Tap
F1
F2
F3
F4
F5
F6
F7
F8
F9
FA
FB
FC
FD
Standard Type 1 Type 3 Type 6
0136
OFF/OFF ON/OFF OFF/ON ON/ON
HEAT COOL HEAT COOL HEAT COOL HEAT COOL
HH HH
HH HH H+ H+
HH
HH HH H+ H+
H H L+ L+
HH HH H+ H+
H H L+ L+
H+ H+
H H L+ L+
L+ L+
LL
LL LL LL LL LL LL LL LL
Slim Duct Type
Tap
F1
F2
F3
F4
F5
F6
F7
F8
F9
FA
FB
FC
FD
SM40 SM45 SM56
Revolution speed (rpm)
1260 1260 1320
1180 1180 1220
1120 1120 1220
1040 1040 1220
1020 1020 1180
990 990 1180
960 960 1180
950 950 1040
910 910 990
870 870 990
840 840 880
790 790 820
550 550 550
3) In heating operation, the mode changes to [UL] if
thermostat is turned off.
4) If Ta ≥ 25°C when heating operation has started and when
defrost operation has been cleared, the air conditioner
operates with (H) mode or higher mode for 1 minute after
Tc entered in E zone of cool air discharge preventive
control (Item 7).
Remarks
Selection of high static
pressure type
Item code:
[5d] or selection of high
static pressure on P.C.
board SW501