Toshiba RAV-SM1404UT-E Air Conditioner User Manual


 
– 111 –
<In case of SP110, SP140>
Correct and clear the cause.
Check wire connection
and correct it.
Correct power supply line.
Check outdoor P.C. board.
Defect Replace
Check wire connection
and correct it.
Correct power supply line.
Is compressor normal?
Is there no refrigerant stagnation?
Does PMV normally operate?
Is it not abnormal overload?
Is power supply voltage normal?
AC198 to 264V
Is power supply voltage normal?
AC198 to 264V
Is wire connection normal?
Compressor lead
(Board side, Compressor side),
Reactor lead, Power supply lead
Is wire connection normal?
Compressor lead
(Board side, Compressor side),
Reactor lead, Power supply lead
Compressor lock Replace
Check outdoor P.C. board.
Defect Replace
Check TE, TS sensors and PMV.
Defect Replace
Check outdoor P.C. board.
Defect Replace
Check outdoor P.C. board.
Defect Replace
YES
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
NO
Check
code
[H01]
[H02]
[H03]
Outdoor
LED display
<Display 1> <Display 2>
l
¥
ll
¡
l
ll
¡
l
¡¡
<Display 1> <Display 2>
ll
l
¥
¡
l
ll
¡
l
¡¡
<Display 1> <Display 2>
l
¥
l
¥
¡
l
ll
¡
l
¡¡
Check and troubleshooting
(Item without special mention Indicates part of outdoor unit.)
[Compressor break down]
[Compressor lock]
[Current detection circuit error]