Toshiba RAV-SM1404UT-E Air Conditioner User Manual


 
– 136 –
YES
NO
Is CN600 connection normal?
Is resistance value of TE sensor normal?
Correct connector.
Sensor error Replace
Check outdoor P.C. board.
Defect Replace
YES
NO
Is CN601 connection normal?
Is resistance value of TD sensor normal?
Correct connector.
Sensor error Replace
Check outdoor P.C. board.
Defect Replace
Check Item code [14].
Correct wiring
of terminal blocks.
Check outdoor P.C. board.
Defect Replace
Correct wiring
and inter-unit cable.
YES
YES
YES
NO
NO
NO
Is setting of group address of remote controller correct?
Are inner wiring and inter-unit cables (1, 2, 3) normal?
Is wiring of terminal blocks (1, 2, 3) normal?
10-2-10. Diagnostic Procedure for Each Check Code (Outdoor Unit)
This section describes the diagnostic method for each check code displayed on the remote controller.
In some cases, a check code indicates multiple symptoms.
Check code
[E04]
Check and troubleshooting
(Item without special mention Indicates part of outdoor unit.)
[Indoor/Outdoor communication error]
[Discharge temp. sensor (TD) error][F04]
[F06]
YES
NO
Is CN602 connection normal?
Is resistance value of TO sensor normal?
Correct connector.
Sensor error Replace
Check outdoor P.C. board.
Defect Replace
[F08] [Outside air temp. sensor (TO) error]
[Heat exchanger temp. sensor (TE) error]
<In case of SP40, SP45>