10-2-10. Diagnostic Procedure for Each Check Code (Outdoor Unit)
• This section describes the diagnostic method for each check code displayed on the remote controller.
In some cases, a check code indicates multiple symptoms.
Check code
[E04]
Check and troubleshooting
(Item without special mention Indicates part of outdoor unit.)
[Indoor/Outdoor communication error]
[Discharge temp. sensor (TD) error][F04]
[F06]
YES
NO
Is CN602 connection normal?
Is resistance value of TO sensor normal?
Correct connector.
Sensor error → Replace
Check outdoor P.C. board.
Defect → Replace
[F08] [Outside air temp. sensor (TO) error]
[Heat exchanger temp. sensor (TE) error]
<In case of SP40, SP45>