Toshiba RAV-SM1404UT-E Air Conditioner User Manual


 
– 14 –
<Twin type>
: IEC standard
Indoor unit 1 RAV- SM562BT-E SM802BT-E
Model Indoor unit 2 RAV- SM562BT-E SM802BT-E
Outdoor unit RAV- SP1104AT(Z)(ZG)-E SP1404AT(Z)(ZG)-E
Cooling capacity (kW) 10.0 12.5
Heating capacity (kW) 11.2 14.0
Indoor unit
Power supply 1 phase 230V (220 – 240V) 50Hz
Running current (A) 13.78 – 12.63 17.76 – 16.28
Power consumption (kW) 2.94 3.83
Cooling Power factor (%) 97 98
EER 3.4 3.26
Electrical
Energy efficiency class AA
characteristics
Running current (A) 12.98 – 11.90 15.82 – 14.50
Power consumption (kW) 2.77 3.41
Heating Power factor (%) 97 98
COP 4.04 4.11
Energy efficiency class AA
Fan Centrifugal
Fan unit Standard air flow H/M/L (m³/min.) 13.0 / 11.9 / 9.8 19.0 / 16.2 / 13.3
Motor (W) 120 120
Sound pressure level H/M/L (dB•A) 40 / 37 / 33 40 / 37 / 34
Sound power level H/M/L (dB•A) 55 / 52 / 48 55 / 52 / 49
Outdoor unit
Power supply 1 phase 230V (220 – 240V) 50Hz
Standard length (m) 7.5 7.5
Min. length (m) 3 3
Refrigerant
Max. total length (m) 50 50
Refrigerant charging amount
40g/m (31m to 50m)
pipe
(Charge-less up to 30m)
Height
Outdoor lower (m) 30 30
difference
Outdoor higher (m) 30 30
Fan Propeller fan
Fan unit Standard air flow volume (m³/min.) 101 103
Motor (W) 100 + 100 100 + 100
Gas side
Main (mm) 15.9 15.9
Connecting
Sub (mm) 12.7 15.9
pipe
Liquid side
Main (mm) 9.5 9.5
Sub (mm) 6.4 9.5
Sound pressure level Cooling/Heating (dB•A) 49 / 50 51 / 52
Sound power level Cooling/Heating (dB•A) 66 / 67 68 / 69
Revised 2: Jun., 2008