Tamron TS690R Smoke Alarm User Manual


 
Configuration [1.9]
The configuration options are as follows:
00 Bell Is an SAB
When programmed as “Yes” the control panel
bell output applies 0V when active. When
programmed as “No” the control panel bell
output removes 0V when active. (Default =
Yes)
01 User 1 Limited
When programmed as “Yes” user 1 is disabled
from option 8 (Configure Part-Sets) in user
menu 2. When programmed as “No” user 1
has access to all user menus and options.
(Default = Yes)
02 Always Signal Fire
When programmed as “Yes” fire alarm
activations are signalled to the ARC at all
times. When programmed as “No” fire alarm
activations are signalled to the ARC only when
the system is full set. (Default = Yes)
03 Silent 24hr Circuits
When programmed as “Yes” 24hr circuit are
silent. When programmed as “No” 24hr circuits
are audible. (Default = No)
04 Enable Duress
When programmed as “Yes” the reversal of the
first two digits on any passcode will generate a
duress alarm. When programmed as “No” the
reversal of the first two digits on any passcode
will NOT generate a duress alarm. (Default =
No)
05 Invert Abort O/P
When programmed as “Yes” the abort output is
normally active and deactivates for 5 seconds
when an alarm is aborted. When programmed
as “No” the abort output is normally inactive
and activates for 5 seconds when an alarm is
aborted. (Default = No)
06 Monitor Polling Signals
When programmed as “Yes” the system will
monitor the polling signals from all wirefree
detectors. This is transmitted by each detector
every 29 minutes. If this option is enabled and
two consecutive polling signals are not
detected by the control panel, the panel will
ge nerat e a ta mper a larm . W hen
programmed as “No” the system will not
monitor polling signals from wirefree detectors.
(Default = Yes)
07 User Reset
When programmed as “Yes" alarms can be
reset by the user. When programmed as ”No"
alarms can only be reset by the engineer or via
remote reset. (Default = No)
08 Fob can only Unset with Entry
When programmed as “Yes" the 525r remote
setting fob can only be used to unset the
system after the entry timer is started. When
programmed as ”No" the 525r remote setting
fob can be used to unset the system at any
time. (Default = Yes)
09 Passcode and "ENT"
When programmed as “Yes", all passcodes
require an additional press of the [ENT] key to
ga in acces s t o t he syste m. When
programmed as ”No", access to the system
only requires the entry of the passcode.
(Default = No)
10 Loud Chime Tones
When programmed as “Yes” the chime tones
are always at full volume. When programmed
as “No” the chime tones are at the level set by
VR1 on the main PCB. (Default = Yes)
11 Do Battery Test
When programmed as "Yes" the control panel
battery and any monitored PSU batteries are
tested every hour and when exiting the
engineer's mode. When programmed as "No"
the control panel battery and any monitored
PSU batteries are not tested. (Default = No)
12 F.Exit is Night
When programmed as “Yes" final exit circuits
change to night circuits when the system is part
set. When programmed as ”No" final exit
circuits remain as final exit circuits when the
system is part set. (Default = No)
13 Mimic Alarms and Faults
When programmed as “Yes” any outputs
programmed as the type "Circuit Alarm" will
activate when the relevant circuit is in alarm or
in a fault condition. When programmed as
“No” any outputs programmed as the type
"Circuit Alarm" will activate when the relevant
circuit is in alarm. (Default = No)
31
TS690R Installation Manual Engineer’s Menu 1