11. Error Code Messages
Error Code Messages
* If the safety devices activate while either (or both) the heater and air purifier are operating, both
will cease operating.
* When the unit is off, press the “override” and “
” buttons simultaneously for at least 2.5 seconds
to display the following at 2.5 second intervals in this order:
Error History (No. 1 (most recent) ~ No. 5);
Estimated Combustion Time (x100H);
Combustion Frequency (x100 times);
Estimated Air Purifier Operation Time (x100H); and
Actual Air Purifier Operation Time (x100H).
* When the unit is off, press the “override” and “
” and “
” buttons simultaneously for 2.5 seconds
to reset Error History and Actual Air Purifier Operation Time.
Error
Code
Content Diagnostic Check Point
00 Power re-instatement while ON/OFF switch ON -
03 Gas interrupted due to Tilt Switch activation Check Tilt Switch
05 Detection of Loose Primary Filter Check Primary Filter
11 Mis-ignition Check Thermocouple Output
12 Incomplete Combustion Activation
Flame Failure
Check Thermocouple Output
14 Overheat Thermistor Activation Check Overheat Thermistor
14 Reverse Flame Safety Device Check Reverse Flame Sensor
Switch
14 Thermal Fuse Melted Check Thermal Fuse
16
High Temp. Cut off (10 minutes at > 40 C)
Check Room Temperature
Thermistor
31 Room Temperature Thermistor broken circuit Check Room Temperature
Thermistor
32 Room Temperature Thermistor short circuit Check Room Temperature
Thermistor
33 Overheat Thermistor broken circuit Check Overheat Thermistor
34 Overheat Thermistor short circuit Check Overheat Thermistor
62 Faulty Fan Motor rpm Check Convection Fan Motor
70 Heater ON/OFF switch abnormal Check Control PCB
(ON/OFF Switch)
71 Solenoids or modulating valve circuit abnormal -
72 Thermocouple initial value abnormal Check Thermocouple output
72 Thermocouple high cut-out
(> 48mV for 5 secs)
Check Thermocouple output
73
Communication Error between PCB & E
2
PROM
-
°