Weight of product:
PUHY-400 PUHY-500 PUHN-200 PUHN-250
430 kg 470 kg 240 kg 255 kg
Caution:
Be very careful to carry product.
- Do not have only one person to carry product if it is more than 20 kg.
- PP bands are used to pack some products. Do not use them as a
mean for transportation because they are dangerous.
- Do not touch heat exchanger fins with your bare hands. Otherwise you
may get a cut in your hands.
- Tear plastic packaging bag and scrap it so that children cannot play
with it. Otherwise plastic packaging bag may suffocate children to death.
- When carrying in outdoor unit, be sure to support it at four points. Car-
rying in and lifting with 3-point support may make outdoor unit unsta-
ble, resulting in a fall of it.
7. Lifting method and weight of product
Dangerous!
When carrying the unit suspended, pass the ropes under the unit
and use the two suspension points each at the front and rear.
Always lift the unit with ropes attached at four points so that impact is
not applied to the unit.
Attach the ropes to the unit at an angle of 40° or less.
Use two ropes at least A m long.
B
A
A 40° or less
B Rope suspension part
A =
7 ··· PUHN-200/250YMC
8 ··· PUHY-400/500YMC
6.2. Collective installation and continu-
ous installation
Space required for collective installation and continuous installation:
When installing several units, leave the space between each block as
shown below considering passage for air and people.
D
D
B
B
B
CC
CC
B
FE
G
EE
A
A
A
A
D D
B
B
B
A
A
A
CCCC
FEFFF
G
C
C
E
A (Must be open)
B Wall height (H)
C Front
D 1000 mm or more
E 250 mm or more
F 450 mm or more
G 900 mm or more
Note:
Open in the two directions
In case wall height (H) exceeds overall height of unit, add h
dimension (h = wall height <H> overall height of unit) to
marked dimension.
If there is a wall at both the front and the rear of the unit, install
up to three units consecutively in the side direction and provide
a space of 1000 mm or more as inlet space/passage space for
each three units.