Enviro VENTED GAS FIREPLACE HEATER Indoor Fireplace User Manual


 
The minimum clearance to combustibles is 6” (150 mm) when using single wall venting and 1” (25 mm)
when using “B-vent” venting.
We strongly recommend installing an approved chimney liner in an existing brick chimney. This will
maximize the potential draft of the chimney and lessen the effects of slow chimney start-up.
VENTING OF A FIREPLACE FITTED WITH THE DRAFTHOOD ADAPTOR:
Note: Please refer to the chimney manufacturer’s installation instructions prior to commencing the
installation.
Figure 40: Unit top venting styles.
 

 



 
  

Figure 42: Draft test place.
Figure 41: Unit rear venting
style.
mm) must be maintained between the vent connector and any combustibles.
CAUTION: A minimum vent height of 12’ (3.6 m) from the oor is required to effectively vent this
replace.
This unit may be vented to an existing masonry
chimney, or where no masonry chimney is available,
an approved “B-vent” chimney, or any other approved
constructed chimney/vent system (see Figure 40 &
41).
In either case, the replace may be connected to
the chimney/vent using a 4” (10 cm) single wall vent
connector.
When an existing masonry chimney is utilized for
the venting, we recommend the vent connector be
connected to an approved 4” (10 cm) diameter ue
liner running the full height of the chimney. In many
jurisdictions this ue liner may be mandatory.
If 4” (10 cm) single wall vent is used, a minimum of
6” (15 cm) must be maintained between the vent
connector and any combustibles.
If 4” (10 cm) “B-vent” is used a minimum of 1” (25
Initial Installation
SPILLAGE TEST:
A spillage test must be performed prior
to leaving the installed replace with the
customer. Perform this test in the following
manner:
1. Close all windows and doors in the room.
2. Start all exhaust fans in the house and the
furnace blower.
3. Light the replace and set to maximum
ame adjustment.
4. After a minimum of 10 minutes operation,
test the chimney draft with a smoke match
at the top row of the pattern to conrm
that there is adequate draft or ‘pull’ at the
openings around the body of the Drafthood
Adaptor, as shown in Figure 43.
26