Enviro VENTED GAS FIREPLACE HEATER Indoor Fireplace User Manual


 
Trouble Shooting
Problem Possible Cause Solution
The main burner does not
ignite when called for.
The gas valve may not be on. • Check that the gas control knob is in the “ON” position.
Thermostat is not calling for
heat.
• Adjust the thermostat several degrees above ambient
temperature.
Problem with gas valve. • Use a DC voltmeter to measure the voltage across the
TPTH and TP terminals. Main operator voltage: Open
circuit ≥ 325mV Closed circuit ≥ 100mV
• If voltage is not present, check the control circuit for
proper operation.
• If proper control system voltage is present, replace the
gas control.
Spark will not light the pilot
after repeatedly pressing the
spark ignitor.
Defective piezo ignitor. • Check connections to ignitor.
• If ignitor connections are good but no spark, replace
ignitor.
Broken spark electrode. • Check for broken ceramic insulation, replace electrode if
broken.
Misaligned spark electrode. • If spark is not arcing from electrode to pilot, loosen the
screws on the pilot base adjust and tighten.
Pilot will not remain lit. Problem with thermocouple
circuit.
• Check for proper connection of the thermocouple to the
rear of the valve. If loose, fully tighten.
• Check pilot for full ame impingement around
thermocouple. If ame is too small, check gas pressure,
adjust pilot rate screw, check pilot head for damage.
• Check thermocouple voltage at valve. It must be greater
than 5 mV. If low, replace thermocouple.
Air in gas line (pilot dies while
knob is depressed).
• Bleed line.
• Check gas line pressure.
• Contact dealer.
Burners will not remain lit. Problem with thermopile
circuit.
• Check gas line pressure .
• Check for ame impingement on thermopile. If low, see
“Pilot will not remain lit”.
• Check thermopile for minimum of 300 mV when burner is
switched on.
• Check wiring to thermostat for breaks.
Flame lifting Leak in vent pipe • Check for leaks in vent connections.
Improper vent conguration • Check vent conguration with manual.
Terminal may be recirculating
ue gases
• Check to see if terminal is on correctly.
• May need to install high wind termination cap.
• Contact dealer.
Glass fogs up Normal Condition: after the appliance warms up the glass will clear.
**Due to additives in gas, glass may get hazy during operation** Clean as needed.
Blue Flames Normal during start up: ames will yellow as the replace heats up.
Flames are burning “dirty” or
sooting
Flame impingement • Check log positioning.
• Increase primary air by opening the venturi shutter and/
or by opening the vent restrictor.
See also “Burners will not remain lit.”
Remote control doesn’t work Problem with the remote • One or more of the batteries are dead. See remote
control instructions.
Problem with replace • The on/off switch is turned to OFF.
• The gas control valve is turned to PILOT or OFF.
• The pilot has gone out.
34