Enviro VENTED GAS FIREPLACE HEATER Indoor Fireplace User Manual


 
29
Initial Installation
GAS LINE CONNECTION AND TESTING:
WARNING: Only persons licensed to work with gas piping may make the necessary gas connections to
this appliance.
GAS LINE CONNECTION
This stove is equipped with a certied exible pipe located on the right side of the unit terminating in
a ” male NPT tting. Consult your local authorities codes or the CAN/CGA B 149 (1 or 2) installation
code in Canada, or in the USA gas installations follow either local codes or the current edition of the
National Fuel Gas Code ANSI Z223.1.
The efciency rating of this appliance is a product thermal efciency rating determined under
continuous operating conditions and was determined independently of any installed system.
The appliance and its shutoff valves must be
disconnected from the gas supply piping system
during any pressure testing where the pressure
exceeds  PSIG (3.45 KPa) or damage will occur
to the valve.
The appliance must be isolated from the gas supply
piping system by closing its individual manual
shutoff valve during any pressure testing of the gas
supply piping system at test pressures equal to or
less than  psig (3.45 KPa).
Always check for gas leaks with a soap
and water solution after completing the
required pressure test.
TO TEST VALVE PRESSURES
The pressure taps are located on the left side of the valve
Turn set screw 1 turn counter clockwise to loosen,
Place
5
/16” (8 mm) I.D. hose over pressure tap system.
Check pressures using a manometer.
When nished, release pressure, remove hose & tighten set screw.
Table 6: Pressure and BTU Information.
Natural Gas Propane
Main Burner #48 DMS #57 DMS
Manifold Pressure 3.8” W.C. / 0.95KPa 11.0” W.C. / 2.7KPa
Min. Manifold Pressure 1.1” W.C. / 0.27KPa 2.7” W.C. / 0.67KPa
Max Supply Pressure 7.0” W.C. / 1.74KPa 13.0” W.C. / 3.28KPa
Min. Supply Pressure 5” W.C. / 1.24KPa 12.0” W.C. / 2.98KPa
Max BTU/hr Input 17,000 BTU/hr / 4.98KW 16,000 BTU/hr / 4.68KW
Min. BTU/hr Input 10,000 BTU/hr / 2.93KW 8,000 BTU/hr / 2.34KW
NEVER USE AN OPEN FLAME FOR LEAK TESTING.