Enviro 6G50 76N Water Heater User Manual


 
19
TERMINATION CLEARANCES SIDEWALL POWER VENT
V X
VENT TERMINAL AIR SUPPLY INLETAREA WHERE TERMINAL IS NOT PERMITTED
v
v
A
G
V
FIXED
CLOSED
FIXED
CLOSED
OPERABLE
OPERABLE
V
C
B
B
B
B
F
B
V
V
A
J
V
H
M
X
X
V
V
K
B
E
D
L
POWER VENT
(using room air for combustion)
EXTERIOR CLEARANCES FOR SIDEWALL VENT TERMINATION
FIGURE 15.
Vent terminal clearances for “Power Vent” installations. Power Vent congurations use room air for combustion.
CANADIAN INSTALLATIONS CANADIAN INSTALLATIONS
A
Clearance above grade,
veranda, porch, deck or
balcony
12 inches (30 cm)
H
Clearance to each side
of center line extended
above meter/regulator
assembly
3 feet (91 cm) within a height 15 feet
(4.5 m) above the meter/
regulator assembly
B
Clearance to window
or door that may be
opened
6 inches (15 cm) for appliances up to
10,000 Btu/hr (3 kW), 12 inches (30
cm) for appliances between 10,000
Btu/hr (3 kW) and 100,000 Btu/hr (30
kW), 36 inches (91 cm) for appliances
above 100,000 Btu/hr (30 kW)
I
Clearance to service
regulator vent outlet
3 feet (91 cm)
C
Clearance to
permanently closed
window
12 inches (30 cm)*
J
Clearance to a non
mechanical air supply
inlet into building or
combustion air inlet to
any other appliance
6 inches (15 cm) for appliances up
to 10,000 Btu/hr (3 kW), 12 inches
(30 cm) for appliances between
10,000 Btu/hr (3 kW) and 100,000
Btu/hr (30kW), 36 inches (91cm)
for appliances above 100,000 Btu/
hr (30 kW)
D
Vertical clearance to
ventilatedsoftlocated
above the terminal
within a horizontal
distance of 2 feet (61
cm) from the center line
of the terminal
12 inches (30 cm)*
K
Clearance to a
mechanical air supply
inlet
6 feet (1.83 m)
E
Clearance to
unventilatedsoft
12 inches (30 cm)*
L
Clearance above paved
sidewalk or paved
driveway located on
public property
7 feet (2.13 m)†
F
Clearance to outside
corner
2 feet (60 cm)*
M
Clearance under
veranda, porch, deck, or
balcony
12 inches (30 cm) ‡
G
Clearance to inside
corner
18 inches (45 cm)*
In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.
† A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
‡Permittedonlyifveranda,porch,deck,orbalconyisfullyopenonaminimumoftwosidesbeneaththeoor.
*Clearanceinaccordancewithlocalinstallationcodesandtherequirementsofthegassupplierandthemanufacturer’sinstallationinstructions.
VENT PIPE TERMINATION
Therststepistodeterminewheretheventpipewillterminate.See
Figures 15, 20 and 21. The vent may terminate through a sidewall
as shown in Figure 20 or through the roof as shown in Figure 21.
The vent system must terminate so that proper clearances are
maintained as cited in local codes or the current edition of the Natural
Gas and Propane Installation Code (CAN/CSA-B149.1).
Instructions on proper installation through a sidewall are provided
in Figure 15.
Plan the vent system layout so that proper clearances are maintained
from plumbing and wiring.
Ventpipesservingpowerventedappliancesareclassiedbybuilding
codes as “vent connectors”. Required clearances from combustible
materials must be provided in accordance with information in
this manual under LOCATING THE NEW WATER HEATER and
INSTALLING THE WATER HEATER, and with the Natural Gas and
Propane Installation Code (CSN/CSA-B149.1) and local codes.