Emerson Process Management CI-9110 Thermostat User Manual


 
CI-9110 6-3 Specifications
Hysteresis: (Output to gauge) 0.5% of span
Motor Protection: Adjustable mechanism limits restrict output
for over and under range conditions.
Automatic timeout prevents clutch wear.
Power Failure: Mechanism maintains output pressure prior
to loss or drop of supply voltage.
6.9 PRESSURE REGULATOR ASSEMBLY
Output Ranges Offered: Range
Factory Calibrated with
3 - 15 psig 20 psig supply
3 - 27 psig 30 psig supply
6 - 30 psig 35 psig supply
Supply Pressure Range: Type Min. Max.
Unit Supply Supply
(psig)
(psig) (psig)
3 - 15 20 100
3 - 27 30 100
6 - 30 35 100
Supply Pressure Effect: 0.1 psig Max. change in output for each 10
psig change of input.
Connection: IN, OUT and VENT ports (1/4 Inch NPT)
6.10 INSTRUMENT ENCLOSURE
Type of Case: Weatherproof and explosion proof. Cast
aluminum with gasketed screw-on cover.
Gray epoxy finish. Meets NEMA-3
specifications
General Dimensions: 6 inch (152.4 mm) diameter
7 inch (176.8 mm) length
Weight: 10 pounds (4.54 kg)
Mounting Options: In-line pressure pipe or 2 inch pipe bracket
6.11 ENVIRONMENTAL
Temperature Limits: -20° to +150° F (-29° to +65° C) Operating
-40° to +185° F (-40° to +85° C) Storage