Emerson Process Management CI-9110 Thermostat User Manual


 
Installation 2-2 CI-9110
2.3 PRESSURE CONNECTIONS
Remote Set Regulators are furnished in models that provide 3-15, 3-27 or 6-30 psig outputs.
All models will accept 100 psig maximum on the supply side. Pressure supplies that exceed
this value will require an external pressure regulator or limiter.
Figure 2-1 - Overall Mounting Dimensions
2.3.1 General Piping
A basic piping diagram is shown in Figure 2-3. The pressure supply line may include a
pressure gauge, external regulator, filter and a shutoff valve as shown. Union type
connections are recommended for pressure lines to allow an easy disconnect. A pressure