Emerson Process Management CI-9110 Thermostat User Manual


 
Field Wiring 4-2 CI-9110
Table 4-1 - Terminal Identification For Analog Input Models
TERMINAL
LEGEND
FUNCTION
TB1-1
TB1-2
TB1-3
TB1-4
TB1-5
TB1-6
TB2-1
TB2-2
TB2-3
TB2-4
TB2-5
TB2-6
Green Screw
Unused
Unused
Analog In+ (Command Input)
Analog In- (Command Input)
Guard
Guard Com
Unused
Current Out +
Current Out -
Supply +
Supply -
Unused
Chassis
Table 4-2 - Terminal Identification For Raise/Lower Models
TERMINAL
LEGEND
FUNCTION
TB1-1
TB1-2
TB1-3
TB1-4
TB1-5
TB1-6
TB2-1
TB2-2
TB2-3
TB2-4
TB2-5
TB2-6
Green Screw
Raise (Command) Input)
Raise Com (Command) Input)
Lower (Command) Input)
Lower Com (Command) Input)
Guard +
Guard Com
Remote/Local Status
Current Out +
Current Out -
Supply +
Supply -
Unused
Chassis
Note: Raise, Lower & Guard Terminals are
non-polarized and opto-isolated.
4.3 ANALOG VOLTAGE INPUT (1-5 V) WITH GUARD
A voltage signal can be used as the Command Input as shown in Figure 4-2. In this
example, a Bristol Babcock, METATONE B, Analog FSK Tone Receiver (Model 8772-31B)
provides the input to the Remote Set Regulator. Switch SW2-8 must be set to the OPEN
position to accommodate a 1-5 V input.