Carrier 50EW Air Conditioner User Manual


 
Table 23 I/O Channel Designations Expansion
Module CV and VAV
TERMINAL
NO.
ASSIGNMENT
T1-2
T3-4
T5-6
T7-8
T9-10
T11-12 IAQ Indoor AI (2-10 vdc)
T13-14 IAQ Outdoor — AI (2-10 vdc)
T15-16
T17-25 Fan Status DI (24 vac)
T18-25 Filter Status DI (24 vac)
T19-25 Field Applied Status DI (24 vac)
T20-25 Demand Limit DI (24 vac)
T21-25 Fire Unit Shutdown DI (24 vac)
T22-25 Fire Pressurization DI (24 vac)
T23-25 Fire Evacuation DI (24 vac)
T24-25 Fire Smoke Purge DI (24 vac)
T26-27
T28-29
T30-29 Alarm Light Indicator DO (24 vac)
T31-32 Power Exhaust Fire #1 DO (115 vac)
T33-32 Power Exhaust Fire #2 DO (115 vac)
T34-35 Power Exhaust Fire #3 DO (115 vac)
T36-35 Power Exhaust Fire #4 DO (115 vac)
T37-38
T39-38
K1
K2
K3
LEGEND
AI Analog Input
DI Direct Input
DO Direct Output
IAQ Indoor Air Quality
T—Terminal
51