Carrier 50EW Air Conditioner User Manual


 
Table 4 Electrical Data 50EJ,EK,EW,EY024-048
UNIT
SIZE
NOMINAL
VOLTAGE
(3 Ph 60 Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM IFM
POWER
EXHAUST
ELECTRIC
HEAT*
POWER SUPPLY
No. 1 No. 2
Min Max RLA LRA RLA LRA Qty Hp FLA (ea) Hp FLA FLA LRA kW FLA MCA MOCP†
024
208/230 187 254 39.1 228 25.6 160 2 1 5.3
5
16.7/
15.2
101.8/100.3 125/125
23.6 41.6 125.4/123.9 150/150
29/36 75.1/ 86.6 114.7/127.3 125/150
23.6 41.6 29/36 75.1/ 86.6 144.2/156.8 150/175
59/72 150.1/173.2 171.0/192.2 200/225
23.6 41.6 59/72 150.1/173.2 200.5/221.7 225/225
10
30.8/
28.0
115.9/113.1 150/150
23.6 41.6 139.5/136.7 175/175
29/36 75.1/ 86.6 132.3/143.3 150/150
23.6 41.6 29/36 75.1/ 86.6 161.8/172.8 175/175
59/72 150.1/173.2 188.6/208.2 220/225
23.6 41.6 59/72 150.1/173.2 218.1/237.7 250/250
15
46.2/
42.0
131.3/127.1 150/150
23.6 41.6 154.9/150.7 175/175
29/36 75.1/ 86.6 151.6/160.8 175/175
23.6 41.6 29/36 75.1/ 86.6 181.1/190.3 200/200
59/72 150.1/173.2 207.9/225.7 250/250
23.6 41.6 59/72 150.1/173.2 237.4/255.2 275/275
460 414 508 19.9 114 11.5 80 2 1 2.7
5 7.6
49.4 60
12.6 23.6 62.0 80
36 43.3 63.6 70
12.6 23.6 36 43.3 79.4 80
72 86.6 96.1 110
12.6 23.6 72 86.6 111.9 125
10 14
55.8 70
12.6 23.6 68.4 80
36 43.3 71.6 80
12.6 23.6 36 43.3 87.4 90
72 86.6 104.1 110
12.6 23.6 72 86.6 119.9 125
15 21
62.8 80
12.6 23.6 75.4 90
36 43.3 80.4 90
12.6 23.6 36 43.3 96.1 100
72 86.6 112.9 125
12.6 23.6 72 86.6 128.6 150
575 518 632 16.0 91 9.6 64 2 1 2.4
5 6.1
40.5 50
12.6 23.6 53.1 60
36 34.6 50.9 60
12.6 23.6 36 34.6 66.7 70
72 69.3 76.9 80
12.6 23.6 72 69.3 92.7 100
10 11
45.4 60
12.6 23.6 58.0 70
36 34.6 57.1 60
12.6 23.6 36 34.6 72.8 80
72 69.3 83.0 90
12.6 23.6 72 69.3 98.8 100
15 17
51.4 60
12.6 23.6 64.0 80
36 34.6 64.6 70
12.6 23.6 36 34.6 80.3 90
72 69.3 90.5 100
12.6 23.6 72 69.3 106.3 110
LEGEND
FLA Full Load Amps
HACR Heating,Air Conditioning and Refrigeration
IFM Indoor (Evaporator) Fan Motor
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
NEC National Electrical Code
OFM Outdoor (Condenser) Fan Motor
RLA Rated Load Amps
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v, and 575 v.
If power distribution voltage to unit varies from rated heatervoltage, heater kW will
vary accordingly.
†Fuse or HACR circuit breaker.
NOTES:
1. Incompliance with NECrequirements formultimotor andcombination loadequip-
ment (refertoNECArticles 430and 440),the overcurrentprotective devicefor the
unit shall be fuse or HACR breaker. The Canadian units may be fuse or circuit
breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motorwhere a phase imbalancein supply voltage is greaterthan
2%.
Use the following formula to determine the percent of voltage imbalance.
max voltage deviation from average voltage
% Voltage Imbalance = 100 x
average voltage
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
3
1371
=
3
= 457
Determine maximum deviation from average voltage.
(AB) 457 − 452 = 5 v
(BC) 464 − 457 = 7 v
(AC) 457 − 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
7
% Voltage Imbalance = 100 x
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.
3. MCAcalculation for units with electric heaters over 50kW = (1.25 x IFM amps) +
(1.00 x heater FLA).
17