Carrier 50EW Air Conditioner User Manual


 
Table 3 Electrical Data 50EJ,EK,EW,EY024-048 (cont)
UNIT
SIZE
NOMINAL
VOLTAGE
(3 Ph 60 Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM IFM
POWER
EXHAUST
ELECTRIC
HEAT*
POWER SUPPLY
No. 1 No. 2
Min Max RLA LRA RLA LRA Qty Hp FLA (ea) Hp FLA FLA LRA kW FLA MCA MOCP†
048
208/230 187 254 82.1 446 69.2 345 4 1 5.3
20
59.4/
54.0
252.4/247.0 300/300
23.6 41.6 276.0/270.6 300/300
29/36 75.1/ 86.6 252.4/247.0 300/300
23.6 41.6 29/36 75.1/ 86.6 276.0/270.6 300/300
59/72 150.1/173.2 252.4/247.0 300/300
23.6 41.6 59/72 150.1/173.2 276.0/270.6 300/300
25
74.8/
68.0
267.8/261.0 300/300
23.6 41.6 291.4/284.6 300/300
29/36 75.1/ 86.6 267.8/261.0 300/300
23.6 41.6 29/36 75.1/ 86.6 291.4/284.6 300/300
59/72 150.1/173.2 267.8/261.0 300/300
23.6 41.6 59/72 150.1/173.2 291.4/284.6 300/300
30
88.0/
80.0
281.0/273.0 300/300
23.6 41.6 304.6/296.6 350/300
29/36 75.1/ 86.6 281.0/273.0 300/300
23.6 41.6 29/36 75.1/ 86.6 304.6/296.6 350/300
59/72 150.1/173.2 281.0/273.0 300/300
23.6 41.6 59/72 150.2/173.2 304.6/296.6 350/300
460 414 508 42.3 223 28.8 173 4 1 2.7
20 27
119.5 150
12.6 23.6 132.1 150
36 43.3 119.5 150
12.6 23.6 36 43.3 132.1 150
72 86.6 120.4 150
12.6 23.6 72 86.6 136.1 150
25 34
126.5 150
12.6 23.6 139.1 175
36 43.3 126.5 150
12.6 23.6 36 43.3 139.1 175
72 86.6 129.1 150
12.6 23.6 72 86.6 144.9 175
30 40
132.5 150
12.6 23.6 145.1 175
36 43.3 132.5 150
12.6 23.6 36 43.3 145.1 175
72 86.6 136.6 175
12.6 23.6 72 86.6 152.4 175
575 518 632 34.6 164 26.7 120 4 1 2.4
20 22
101.6 125
12.6 23.6 114.2 125
36 34.6 101.6 125
12.6 23.6 36 34.6 114.2 125
72 69.3 101.6 125
12.6 23.6 72 69.3 114.2 125
25 27
106.6 125
12.6 23.6 119.2 150
36 34.6 106.6 125
12.6 23.6 36 34.6 119.2 150
72 69.3 106.6 125
12.6 23.6 72 69.3 119.2 150
30 32
111.6 125
12.6 23.6 124.2 150
36 34.6 111.6 125
12.6 23.6 36 34.6 124.2 150
72 69.3 111.6 125
12.6 23.6 72 69.3 124.2 150
LEGEND
FLA Full Load Amps
HACR Heating,Air Conditioning and Refrigeration
IFM Indoor (Evaporator) Fan Motor
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
NEC National Electrical Code
OFM Outdoor (Condenser) Fan Motor
RLA Rated Load Amps
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v, and 575 v.
If power distribution voltage to unit varies from rated heatervoltage, heater kW will
vary accordingly.
†Fuse or HACR circuit breaker.
NOTES:
1. Incompliance with NECrequirements formultimotor andcombination loadequip-
ment (refertoNECArticles 430and 440),the overcurrentprotective devicefor the
unit shall be fuse or HACR breaker. The Canadian units may be fuse or circuit
breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motorwhere a phase imbalancein supply voltage is greaterthan
2%.
Use the following formula to determine the percent of voltage imbalance.
max voltage deviation from average voltage
% Voltage Imbalance = 100 x
average voltage
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
3
1371
=
3
= 457
Determine maximum deviation from average voltage.
(AB) 457 − 452 = 5 v
(BC) 464 − 457 = 7 v
(AC) 457 − 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
7
% Voltage Imbalance = 100 x
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.
3. MCAcalculation for units with electric heaters over 50kW = (1.25 x IFM amps) +
(1.00 x heater FLA).
23