Carrier 48SX024-060 Gas Heater User Manual


 
REQ’D CLEARANCES FOR SERVICING. in. (mm)
Duct panel .............................0
Unit top ...........................36(914)
Side opposite ducts .....................36(914)
Compressor access .....................36(914)
(Except for NEC requirements)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)
Maximum extension of overhangs ...............48(1219)
Unit top ...........................14(356)
Duct side of unit ........................2(51)
Side opposite ducts .....................14(356)
Bottom of unit ...........................0
Flue panel .........................36(914)
NEC REQ’D CLEARANCES. in. (mm)
Between units, control box side ................42(1067)
Unit and ungrounded surfaces, control box side .........36(914)
Unit and block or concrete walls and other grounded
surfaces, control box side ..................42(1067)
UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WEIGHT
CORNER WEIGHT
(lb/kg)
lb kg A B C D
48SS048080 208/230-1-60, 208/230-3-60, 460-3-60 438 199 113/51 89/40 164/75 72/33
48SS048100/120/140 208/230-1-60, 208/230-3-60, 460-3-60 450 205 116/53 92/42 165/75 77/35
48SS060080 208/230-1-60, 208/230-3-60, 460-3-60 477 217 123/56 99/45 173/79 82/37
48SS060100/120/140 208/230-1-60, 208/230-3-60, 460-3-60 489 222 126/57 102/46 173/79 88/40
UNIT
CENTER OF GRAVITY (in./mm)
XYZ
48SS048080 28.54/724.9 20.00/508 17.66/448.6
48SS048100/120/140 28.22/716.8 20.05/509.3 17.66/448.6
48SS060080 28.18/715.6 20.19/512.8 17.66/448.6
48SS060100/120/140 27.79/705.9 20.23/513.8 17.66/448.6
LEGEND
CG Center of Gravity
COND Condenser
LV Low Voltage
MAT’L Material
NEC National Electrical Code
REQ’D Required
NOTES:
1. Clearances must be maintained toprevent recirculation of air from outdoor-
fan discharge.
2. Adequate clearance around air openings into combustion chamber must
be provided.
Fig. 5 48SS048,060 With Optional Base Rail, Unit Dimensions