Carrier 48SX024-060 Gas Heater User Manual


 
REQ’D CLEARANCES FOR SERVICING. in. (mm)
Duct panel .............................0
Unit top ...........................36(914)
Side opposite ducts .....................36(914)
Compressor access .....................36(914)
(Except for NEC requirements)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)
Maximum extension of overhangs ...............48(1219)
Unit top ...........................14(356)
Duct side of unit ........................2(51)
Side opposite ducts .....................14(356)
Bottom of unit ...........................0
Flue panel .........................36(914)
NEC REQ’D CLEARANCES. in. (mm)
Between units, control box side ................42(1067)
Unit and ungrounded surfaces, control box side .........36(914)
Unit and block or concrete walls and other grounded
surfaces, control box side ..................42(1067)
UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WEIGHT
CORNER WEIGHT
(lb/kg)
lb kg A B C D
48SS048080 208/230-1-60, 208/230-3-60, 460-3-60 414 188 107/49 83/38 158/72 66/30
48SS048100/120/140 208/230-1-60, 208/230-3-60, 460-3-60 426 193 110/50 86/39 159/72 71/32
48SS060080 208/230-1-60, 208/230-3-60, 460-3-60 453 206 117/53 93/42 167/76 76/35
48SS060100/120/140 208/230-1-60, 208/230-3-60, 460-3-60 465 211 120/55 96/44 167/76 82/37
UNIT
CENTER OF GRAVITY (in./mm)
XYZ
48SS048080 28.76/731 23.46/596 15.35/390
48SS048100/120/140 28.42/722 23.42/595 15.35/390
48SS060080 28.36/720 23.27/591 15.35/390
48SS060100/120/140 27.95/710 23.23/590 15.35/390
LEGEND
CG Center of Gravity
COND Condenser
LV Low Voltage
MAT’L Material
NEC National Electrical Code
REQ’D Required
NOTES:
1. Clearances must be maintained toprevent recirculation of air from outdoor-
fan discharge.
2. Adequate clearance around air openings into combustion chamber must
be provided.
Fig. 4 48SS048,060 Without Base Rail, Unit Dimensions
4