D9112B | Program Entry Guide | 2.0 Area Wide Parameters EN | 29
Bosch Security Systems | 2/04 | 74-06145-000-D
A# Single Ring
This program item determines if an alarm from a
non-fire point can restart the alarm bell time with
each alarm event, or only initiate alarm output once
per arming period.
This does not silence the command center alarm bell
tone, nor prevent any reports. This feature does not
affect fire points. Fire points restart bell time with
each new alarm.
Default: No
Selection: Yes or No
Yes
One bell output per arming. After one
alarm during the armed period, alarms
on non-fire points in the same area
cannot restart the bell.
No
Restart bell output with each alarm
event.
A# Bell Test
Default: No
Selection: Yes or No
Provide alarm output from the programmed
Alarm
Bell Relay
for two sec. after arming the area.
In areas that report opening and closing activity, the
bell test happens after the panel sends the
Closing
report and receives the acknowledgement from the
receiver. For proper operation of the bell, test in an
area where closings are reported:
Program a phone number and appropriate
routing for the
Open/Close
report group.
Program
Area O/C
YES.
Do not suppress
Opening
and
Closing
reports
in O/C Windows.
Make sure all users have the authority to
generate
Closing
reports.
Do not restrict
Opening
and
Closing
reports.
If you are using opening and closing windows,
be sure that
Disable O/C in Window
is
programmed NO in Open/Close Options.
In areas that do NOT report opening and closing
activity, the alarm bell relay output for this area is
activated for two sec. after exit time expires. For
proper operation of the bell test, program
Area O/C
NO.
0101
0101
0101
Bell test may be erratic. If several areas
programmed for bell test are armed at the
same time, and all the areas share the same
alarm bell relay, the relay operation may be
erratic, or longer than expected.
For example, if all eight areas are
programmed for bell test, share the same
alarm bell relay, have the same exit delay
time, and are armed at the same time, the
bell may ring for as long as 16 sec. during
the bell test.
2.3 Opening and Closing
Use this programming category to define opening
and closing supervision characteristics for each area
in the D9112. In this category are two programming
modules: Open/Close Options and O/C Windows.
Additional programming in Authority Lvi Assign and
Phone Routing modules can affect
Opening
and
Closing
reports. Bosch Security Systems
recommends that you review all four of these
modules before programming the D9112.
All arming and disarming activities create local
events which are stored in the panel’s event log and
printed on the local printer, if installed.
Programming determines if the reports are sent to
the central station.
About the default programming: To enable
typical area
Opening
and
Closing
report
supervision in Modem II, the only programming
change needed is to select a phone destination for
the reports in Phone Routing,
Open/Close
.
2.3.1 Open and Close Options
There are two different ways to generate
Opening
and
Closing
reports from a D9112. You can
generate
Opening
and
Closing
reports according to
account status and/or according to area status.
Account Opening and Closing Reports
Whether
Account
Opening
and
Closing
reports
are generated or not depends on programming in
A# Acct O/C
in this section of the program.
Area Opening and Closing Reports
Whether
Area
Opening
and
Closing
reports are
generated or not depends on programming in
A#
Area O/C
in this section of the program.