D9112B | Program Entry Guide | 1.0 Panel Wide Parameter EN | 19
Bosch Security Systems | 2/04 | 74-06145-000-D
Ph# Service
Default: Blank
Selection: Blank, P, B, or D
See the introduction to Phone Routing for a
description of the selections.
1.3 Power Supervision
AC Fail Time
Default: 10
Selection: 1 to 90 sec. (Blank and 0 are invalid)
Amount of time (in seconds) that AC power must be
off before the D9112 responds to the AC failure.
The response to restoral of AC power is delayed for
the same amount of time. The panel always monitors
AC. To disable audible and reporting failure
responses, program the following items NO:
AC
,
Fail/Res Rpt
,
AC Tag Along
, and
AC/Battery
Buzz
.
0101
0101
0101
Visual AC Failure Response: When a
failure occurs, the SERVC AC FAIL
message displays at command centers.
You can program other AC failure
responses in the program items that follow,
and you can program a relay to activate in
Relay Parameters.
AC Fail/Res Rpt
AC Power Supervision
reports are sent to the
central station when they occur. To comply with UL
864 requirements for Commercial Fire Systems,
program
AC Fail/RES Rpt
NO.
Default: No
Selection: Yes or No
Yes
AC Failure
and
AC Restoral
reports
are sent to the central station when the
panel generates the event. They are
routed to the telephone number for
Power/Phone
events. AC Failure is
reported as Trouble Zone 0 when
transmitting in BFSK.
No
AC Failure
and
AC Restoral
reports
are NOT sent when they occur. They
can still be sent with subsequent
reports if
AC Tag Along
is
programmed YES.
AC Tag Along
Send
AC Failure
report as an additional message
(tag along) with other reports. To comply with UL
864 requirements for Commercial Fire Systems,
program
AC Tag Along
YES.
Default: No
Selection: Yes or No
Yes When AC fails, the report is not sent
until another event occurs. The
AC
Fail
report is sent to the receiver with
subsequent event reports until the
AC
Restoral
report is sent. These
AC Fail
reports are routed to the phone
destination of the event with which it is
sent. If AC power restores before any
other event occurs, the report is not
sent.
Note:
If both
AC Fail/Res Rpt
and
AC
Tag Along
are YES, two
AC
Failure
reports are sent to the
Power/Phone
telephone number(s),
once as the primary message, and once
as the “tag along” report.
No
AC Fail
reports are not tag along
events.
AC/Battery Buzz
Turn the command center trouble buzzer on when
AC fails or the battery is low or missing. This
program item does not prevent the SERVC AC
FAIL or SERVC BATT LOW displays.
Default: No
Selection: Yes or No
Yes Buzz command center sounder when
AC fails or the battery is low or missing.
To comply with NFPA standards for fire
systems, program this item YES.
No Do not audibly indicate AC failure or
battery trouble on the command center.