Trane PTAC-SVX01C-EN Air Conditioner User Manual


 
PTAC-SVX01C-EN 11
Installation
Table 3. Electric heat capacity and electrical data, models PTEE and PTHE
(i)
Nominal heating Building circuit requirement
Voltage
(ii)
Electric
heater
Size (kW)
# of
stages
Btu/h at
230/208V
Btu/h at
265V
Total
watts
(iii)
Unit
total
amps
Minimum
ampacity
(iv)
Maximum
protection
(v)
Plug
230/208 2.0/1.6 1 6,800/
5,500
- 2000/
1600
8.9/7.9 11.4 15 6 - 15 P
230/208 3.0/2.4 1 10,200/
8,200
- 3000/
2400
13.4/11.8 17 20 6 - 20 P
230/208 5.0/4.0 1 17,100/
13,700
- 5000/
4000
22.2/19.7 28 30 6 - 30 P
265 2.0 1 - 6,800 2000 7.7 9.8 15 7 - 20 P
265 3.0 1 - 10,200 3000 11.6 14.7 15 7 - 20 P
265 5.0 1 - 17,100 5000 19.3 24.4 25 7 - 30 P
(i)
All heat pumps have electric heat.
(ii)
Minimum voltage on 230/208 volt models is 187 volts; maximum is 253 volts. Minimum voltage on 265 volt models is 239 volts; max-
imum is 292 volts.
(iii)
Total watts for 7,000 and 9,000 Btu models; add 70 watts for 12,000 and 15,000 Btu models.
(iv)
Minimum branch circuit ampacity ratings conform to the National Electric Code. However, local codes should apply.
(v)
Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265 volt models must be cartridge-
style time delay fuses.
Table 4. Power receptacle configurations
Unit
Voltage
Rating
230/
208
230/
208
230/
208 265 265
Unit plug
Plug amp
rating
15 20 30 15/20 30
NEMA
designation
6-15P 6-20P 6-30P 7-15P/7-20P 7-30P
Receptacle
Receptacle
amp rating
20 20 30 20 30
NEMA
designation