Trane FIN-PRC004 Air Conditioner User Manual


 
FIN-PRC004-EN82
Performance
Data Security Wall Fin
Table PD-7 Steel Tube/Fin Elements Btu/Hour/Foot
Steam
Rating Hot Water (Ave.)
Steel Tube/Fin Elements with Fully Perforated Enclosures 215°F 220°F 210°F 200°F 190°F 180°F 170°F 160°F 150°F 140°F 130°F
Mtg.
Tube Fin Size Fins/ Encl. Tiers & Height Factor Factor
Size Inches Foot Type Centers Inches 1.00 1.05 0.95 0.86 0.78 0.69 0.61 0.53 0.45 0.40 0.33
S12-SF 1 16 1250 1310 1190 1080 980 860 760 660 560 500 410
S18-SF 1 22 1300 1370 1240 1120 1010 900 790 690 590 520 430
1
1
/4 4
1
/4 x 4
1
/4 40 S18-SF 2-6 22 2250 2360 2140 1940 1760 1550 1370 1190 1010 900 740
F12-SF 1 16 1120 1180 1060 960 870 770 680 590 500 450 370
F18-SF 1 22 1160 1220 1100 1000 900 800 710 610 520 460 380
F18-SF 2-6 22 2080 2180 1980 1790 1620 1440 1270 1100 940 830 690
S12-SF 1 16 1070 1170 1060 960 870 770 680 590 500 450 370
S18-SF 1 22 1110 1190 1080 970 880 780 690 600 510 450 370
1
1
/4 4
1
/4 x 4
1
/4 32 S18-SF 2-6 22 1930 2170 1970 1780 1620 1430 1260 1090 930 830 680
F12-SF 1 16 960 1050 950 860 780 690 610 530 450 400 330
F18-SF 1 22 1000 1060 960 870 780 690 620 530 450 400 340
F18-SF 2-6 22 1790 2010 1820 1650 1490 1320 1170 1010 860 760 630
1. Mounting Height is the dimension from the floor to the top of the enclosure to obtain listed capacities.
2. Two-tier applications can only be used with 18 high enclosures installed on 6 center lines.
Table PD-8 Steel Tube/Fin Elements Watts/Meter
Hot Water (Ave.)
Steel Tube/Fin Elements with Fully Perforated Enclosures 104°C99°C93°C88°C82°C77°C71°C66°C60°C54°C
Mtg. Steam
Tube Fin Size Fins/ Encl. Tiers & Height Rating Factor
Size mm Meter Type Centers mm 102°C 1.05 0.95 0.86 0.78 0.69 0.61 0.53 0.45 0.40 0.33
S12-SF 1 406 1230 1260 1140 1040 940 830 730 630 540 480 390
S18-SF 1 559 1330 1320 1190 1080 970 870 760 660 570 500 410
32 mm 108 x 108 131 S18-SF 2-152 mm 559 2060 2270 2060 1860 1690 1490 1320 1140 970 870 710
F12-SF 1 406 1110 1130 1020 920 840 740 650 570 480 430 360
F18-SF 1 559 1180 1170 1060 960 870 770 680 590 500 440 370
F18-SF 2-152 mm 559 1900 2100 1900 1720 1560 1380 1220 1060 900 800 660
S12-SF 1 406 1060 1080 980 890 810 710 630 540 460 410 340
S18-SF 1 559 1130 1140 1020 930 830 750 650 570 490 430 350
32 mm 108 x 108 105 S18-SF 2-152 mm 559 1770 1950 1770 1600 1450 1280 1140 980 830 750 610
F12-SF 1 406 950 970 880 790 720 640 560 490 410 370 310
F18-SF 1 559 1020 1010 910 830 750 660 580 510 430 380 320
F18-SF 2-152 mm 559 1630 1810 1630 1480 1340 1190 1050 910 770 690 570
1. *I = B = R Rating on Assemblies as marked.
2. Mounting Height is the dimension from the floor to the top of the enclosure to obtain listed capacities.
3. Two-tier applications can only be used with 457 mm high enclosures installed on 152 mm center lines.