Trane FIN-PRC004 Air Conditioner User Manual


 
79FIN-PRC004-EN
Performance
Data Security Wall Fin
Table PD-3 Steel Tube/Fin Elements Btu/Hour/Foot
Hot Water (Ave.)
Steel Tube/Fin Elements with Partially Perforated Enclosures 220°F 210°F 200°F 190°F 180°F 170°F 160°F 150°F 140°F 130°F
Mtg. Steam
Tube Fin Size Fins/ Encl. Tiers & Height Rating Factor
Size Inches Foot Type Centers Inches 1.00 1.05 0.95 0.86 0.78 0.69 0.61 0.53 0.45 0.40 0.33
S12-SP 1 16 1280 1340 1220 1100 1000 880 780 680 580 510 420
S18-SP 1 22 1380 1450 1310 1190 1080 950 840 730 620 550 460
1
1
/4 4
1
/4x4
1
/4 40 S18-SP 2-6 22 2140 2250 2030 1840 1670 1480 1310 1130 960 860 710
F12-SP 1 16 1150 1210 1090 990 900 790 700 610 520 460 380
F18-SP 1 22 1230 1290 1170 1060 960 850 750 650 550 490 410
F18-SP 2-6 22 1980 2080 1880 1700 1540 1370 1210 1050 890 790 650
S12-SP 1 16 1100 1160 1050 950 860 760 670 580 500 440 360
S18-SP 1 22 1180 1240 1120 1010 920 810 720 630 530 470 390
1
1
/4 4 /4x4
1
/4 32 S18-SP 2-6 22 1840 1930 1750 1580 1440 1270 1120 980 830 740 610
F12-SP 1 16 990 1040 940 850 770 680 600 520 450 400 330
F18-SP 1 22 1060 1110 1010 910 830 730 650 560 480 420 350
F18-SP 2-6 22 1700 1790 1620 1460 1330 1170 1040 900 770 680 560
1. *I = B = R Rating on Assemblies as marked.
2. Mounting Height is the dimension from the floor to the top of the enclosure to obtain listed capacities.
3. Two-tier applications can only be used with 18 high enclosures installed on 6 center lines.
Table PD-4 Steel Tube/Fin Elements Watts/Meter
Hot Water (Ave.)
Steel Tube/Fin Elements with Partially Perforated Enclosures 104°C99°C93°C88°C82°C77°C71°C66°C60°C54°C
Mtg. Steam
Tube Fin Size Fins/ Encl. Tiers & Height Rating Factor
Size Inches Foot Type Centers Inches 1.00 1.05 0.95 0.86 0.78 0.69 0.61 0.53 0.45 0.40 0.33
S12-SP 1 406 1230 1290 1170 1060 960 850 750 650 560 490 400
S18-SP 1 559 1330 1390 1260 1140 1040 910 810 700 600 530 440
32 mm 108 x 131 S18-SP 2-152 mm 559 2060 2160 1950 1770 1600 1420 1260 1090 920 830 680
108 F12-SP 1 406 1110 1160 1050 950 870 760 670 590 500 440 370
F18-SP 1 559 1180 1240 1120 1020 920 820 720 620 530 470 390
F18-SP 2-152 mm 559 1900 2000 1810 1630 1480 1320 1160 1010 860 760 620
S12-SP 1 406 1060 1120 1010 910 830 730 640 560 480 420 350
S18-SP 1 559 1130 1190 1080 970 880 780 690 610 510 450 370
32 mm 108 x 105 S18-SP 2-152 mm 559 1770 1860 1680 1520 1380 1220 1080 940 800 710 590
108 F12-SP 1 406 950 1000 900 820 740 650 580 500 430 380 320
F18-SP 1 559 1020 1070 970 870 800 700 620 540 460 400 340
F18-SP 2-152 mm 559 1630 1720 1560 1400 1280 1120 1000 870 740 650 540
1. *I = B = R Rating on Assemblies as marked.
2. Mounting Height is the dimension from the floor to the top of the enclosure to obtain listed capacities.
3. Two-tier applications can only be used with 457 mm high enclosures installed on 152 mm center lines.