Trane FIN-PRC004 Air Conditioner User Manual


 
FIN-PRC004-EN24
Performance
Data
Front
Outlet
Table PD-9 Ratings 4 (102 mm) Deep, Type F - Enclosure With Copper/Aluminum Elements
Steam Capacity Hot Water Capacity
Per Ft.-1 Psi at 65°F Air Btu/Hr./Ft. At 65°F Air, Average Water Temperature
Per Meter - 6.895 kPA Watts/Meter At 18.3°C Air, Average Water Temperature
at 18.3°C Air
Install. 220°F 210°F 200°F 190°F 180°F 170°F 160°F 150°F140°F130°F120°F 110°F 100°F
Fin Series Height EDR 104°C99°C93°C88°C82°C77°C71°C66°C60°C54°C49°C43°C38°C
Per Foot Inches Sq. Ft. Btu/Hr./Ft. IBR Factor Steam to Hot Water
Element Per Meter Tiers Encl. mm Sq. M Watts/Meter 1.05 0.95 0.86 0.78 0.69 0.61 0.53 0.45 0.40 0.33 0.26 0.20 0.15
10F 12
3
/4 4.50 1080 1135 1025 930 840 745 660 570 485 430 355 280 215 160
324 48 1040 1090 986 894 808 716 635 548 466 413 341 269 207 154
14F 16
3
/4 4.75 1140 1195 1085 980 890 785 695 605 515 455 375 295 230 170
425 51 1100 1150 1040 942 856 755 668 582 495 438 361 284 221 163
1 18F 20
3
/4 4.87 1170 1230 1110 1005 910 805 715 620 525 470 385 305 235 175
527 52 1120 1180 1070 966 875 774 688 596 505 452 370 293 226 168
24F 26
3
/4 5.04 1210 1270 1150 1040 945 835 740 640 545 485 400 315 240 180
679 54 1160 1220 1110 1000 909 803 712 615 524 466 385 303 231 173
3
/4 CA 40 2* 14F 16
3
/4 7.23 1735 1820 1650 1490 1355 1195 1060 920 780 695 570 450 345 260
19 mm 131 m 425 78 1670 1750 1590 1430 1300 1150 1020 885 750 668 548 433 332 250
Copper Tube 18F 20
3
/4 7.89 1895 1990 1800 1630 1480 1305 1155 1005 850 760 625 490 380 285
Alum. Fins 527 85 1820 1910 1730 1570 1420 1260 1110 966 817 731 601 471 365 274
Fins 3
1
/4 x 3
1
/4 2** 24F 26
3
/4 8.31 1995 2095 1895 1715 1555 1375 1215 1055 895 800 660 520 400 300
83 x 83 mm 679 89 1920 2020 1820 1650 1500 1320 1170 1010 861 769 635 500 385 288
Thickness .0135 10F 12
3
/4 5.04 1210 1270 1150 1040 945 835 740 640 545 485 400 315 240 180
.34 mm 324 54 1160 1220 1110 1000 909 803 712 615 524 466 385 303 231 173
14F 16
3
/4 5.62 1350 1415 1280 1160 1055 930 825 715 605 540 445 350 270 200
425 60 1300 1360 1230 1120 1010 894 793 688 582 519 428 337 260 192
1 18F 20
3
/4 6.04 1450 1520 1375 1245 1130 1000 885 770 650 580 480 375 290 215
527 65 1390 1460 1320 1200 1090 962 851 740 625 558 462 361 279 207
24F 26
3
/4 6.37 1530 1605 1455 1315 1195 1055 935 810 690 610 505 400 305 230
679 69 1470 1540 1400 1260 1150 1010 899 779 664 587 486 385 293 221
50 2* 14F 16
3
/4 7.37 1770 1860 1680 1520 1380 1220 1080 940 795 710 585 460 355 265
164 m 425 79 1700 1790 1620 1460 1330 1170 1040 904 764 683 563 442 341 255
18F 20
3
/4 8.45 2030 2130 1930 1745 1585 1400 1240 1075 915 810 670 525 405 305
527 91 1950 2050 1860 1680 1520 1350 1190 1030 880 779 644 505 389 293
2** 24F 26
3
/4 8.91 2140 2245 2035 1840 1670 1475 1305 1135 965 855 705 555 430 320
679 96 2060 2160 1960 1770 1610 1420 1260 1090 928 822 678 534 413 308
10F 12
3
/4 5.33 1280 1345 1215 1100 1000 885 780 680 575 510 420 330 255 190
324 57 1230 1290 1170 1060 962 851 750 654 553 490 404 317 245 183
14F 16
3
/4 6.08 1460 1535 1385 1255 1140 1005 890 775 655 585 480 380 290 220
425 65 1400 1480 1330 1210 1100 966 856 745 630 563 462 365 279 212
1 18F 20
3
/4 6.50 1560 1640 1480 1340 1215 1075 950 825 700 625 515 405 310 235
527 70 1500 1580 1420 1290 1170 1030 914 793 673 601 495 389 298 226
24F 26
3
/4 6.98 1675 1760 1590 1440 1305 1155 1020 885 755 670 550 435 335 250
679 75 1610 1690 1530 1380 1260 1110 981 851 726 644 529 418 322 240
58 2* 14F 16
3
/4 7.45 1790 1880 1700 1540 1395 1235 1090 950 805 715 590 465 360 270
190 m 425 80 1720 1810 1640 1480 1340 1190 1050 914 774 688 567 447 346 260
18F 20
3
/4 8.60 2065 2170 1960 1775 1610 1425 1260 1095 930 825 680 535 415 310
527 93 1990 2090 1880 1710 1550 1370 1210 1050 894 793 654 514 399 298
2** 24F 26
3
/4 9.23 2215 2325 2105 1905 1725 1530 1350 1175 995 885 730 575 445 330
679 99 2130 2240 2020 1830 1660 1470 1300 1130 957 851 702 553 428 317
*5
1
/2 (140 mm) Centers
**9
1
/2 (241 mm) Centers
All two tier and 24F high ratings not IBR approved.
Dimensions in bold indicate metric units.
NOTE: Rating is Btu/hr/ft (Watts/meter) of finned length (for element dimensions see page 49). Hot water ratings determined by applying correction factor to steam ratings, are for
water velocities of 3 ft/sec (.91 m/s) or greater. See page 9, Chart S-1 for correction factors for water velocities other than 3 ft/sec (.91 m/s). For definition of installed height and heating
effect factors, see page 11. For heating ratings at other steam pressures and/or entering air temperatures, see page 10, Table S-2.