29FIN-PRC004-EN
Performance
Data
Top
Outlet
Table PD-14 — Ratings 4” (102 mm) Deep, Type T - Enclosures With Copper/Aluminum Elements
Steam Capacity Hot Water Capacity
Per Ft.-1 Psi at 65°F Air Btu/Hr./Ft. — At 65°F Air, Average Water Temperature
Per Meter - 6.895 kPa Watts/Meter — At 18.3°C Air, Average Water Temperature
at 18.3°C Air
Install. 220°F 210°F 200°F 190°F 180°F 170°F 160°F 150°F140°F130°F120°F 110°F 100°F
Fin Series Height EDR 104°C99°C93°C88°C82°C77°C71°C66°C60°C54°C49°C43°C38°C
Per Foot Inches Sq. Ft. Btu/Hr./Ft. IBR Factor — Steam to Hot Water
Element Per Meter Tiers Encl. mm Sq. M Watts/Meter 1.05 0.95 0.86 0.78 0.69 0.61 0.53 0.45 0.40 0.33 0.26 0.20 0.15
10T 13
9
/16 4.12 990 1049 940 850 770 685 605 525 445 395 325 255 200 150
344 44 952 1000 904 817 740 659 582 505 428 380 313 245 192 144
14T 17
9
/16 4.29 1030 1080 980 885 805 710 630 545 465 410 340 270 205 155
466 46 990 1040 942 851 774 683 606 524 447 394 327 260 197 149
1 18T 21
9
/16 4.41 1060 1115 1005 910 825 730 645 560 475 425 350 275 210 160
548 47 1020 1070 966 875 793 702 620 538 457 409 337 264 202 154
24T 27
9
/16 4.58 1100 1155 1045 945 860 760 670 585 495 440 365 285 220 165
700 49 1060 1110 1000 909 827 731 644 563 476 423 351 274 212 159
3
/4” CA 40 2* 14T 17
9
/16 6.52 1565 1645 1485 1345 1220 1080 955 830 705 625 515 405 315 235
19 mm 131 m 466 70 1500 1580 1430 1290 1170 1040 918 798 678 601 495 389 303 226
Copper Tube 18T 21
9
/16 7.14 1715 1800 1630 1475 1340 1185 1045 910 770 685 565 445 345 255
Alum. Fins 548 77 1650 1730 1570 1420 1290 1140 1000 875 740 659 543 428 332 245
Fins 3
1
/4” x 3
1
/4” 2** 24T 27
9
/16 7.41 1780 1870 1690 1530 1390 1230 1085 945 800 710 585 460 355 265
83 x 83 mm 700 80 1710 1800 1620 1470 1340 1180 1040 909 769 683 563 442 341 255
Thickness .0135” 10T 13
9
/16 4.91 1180 1240 1120 1015 920 815 720 625 530 470 390 305 235 175
.34 mm 344 53 1140 1190 1080 976 885 784 692 601 510 452 375 293 226 168
14T 17
9
/16 5.25 1260 1325 1195 1085 980 870 770 670 565 505 415 330 250 190
466 57 1210 1270 1150 1040 942 837 740 644 543 486 399 317 240 183
1 18T 21
9
/16 5.58 1340 1405 1275 1150 1045 925 815 710 605 535 440 350 270 200
548 60 1290 1350 1230 1110 1000 889 784 683 582 514 423 337 260 192
24T 27
9
/16 5.89 1415 1485 1345 1215 1105 975 865 750 635 565 465 370 285 210
700 63 1360 1430 1290 1170 1060 938 832 721 611 543 447 356 274 202
50 2* 14T 17
9
/16 6.89 1655 1740 1570 1425 1290 1140 1010 875 745 660 545 430 330 250
164 m 466 74 1590 1670 1510 1370 1240 1100 971 841 716 635 524 413 317 240
18T 21
9
/16 7.81 1875 1970 1780 1610 1460 1295 1145 995 845 750 620 490 375 280
548 84 1800 1890 1710 1550 1400 1240 1100 957 813 721 596 471 361 269
2** 24T 27
9
/16 8.25 1980 2080 1880 1700 1545 1365 1205 1050 890 790 655 515 395 295
700 89 1900 2000 1810 1640 1490 1310 1160 1010 856 760 630 495 380 284
10T 13
9
/16 5.33 1280 1345 1215 1100 1000 885 780 680 575 510 420 330 255 190
344 57 1230 1290 1170 1060 962 851 750 654 553 490 404 317 245 183
14T 17
9
/16 5.75 1380 1450 1310 1185 1075 950 840 730 620 550 455 360 275 205
466 62 1330 1390 1260 1140 1030 914 808 702 596 529 438 346 264 197
1 18T 21
9
/16 6.20 1490 1565 1415 1280 1160 1030 910 790 760 595 490 385 300 225
548 67 1430 1500 1360 1230 1120 990 875 760 644 572 471 370 288 216
24T 27
9
/16 6.66 1600 1680 1520 1375 1250 1105 975 850 720 640 530 415 320 240
700 72 1540 1615 1460 1320 1200 1060 940 820 690 615 510 400 310 230
58 2* 14T 17
9
/16 7.04 1690 1775 1605 1455 1320 1165 1030 895 760 675 555 440 340 255
190 m 466 76 1620 1710 1540 1400 1270 1120 990 861 731 649 534 423 327 245
18T 21
9
/16 8.20 1970 2070 1870 1695 1535 1360 1200 1045 885 790 650 510 395 295
548 88 1890 1990 1800 1630 1480 1310 1150 1000 851 760 625 490 380 284
2** 24T 27
9
/16 8.81 2115 2220 2010 1820 1650 1460 1290 1120 950 845 700 550 425 315
700 95 2030 2140 1930 1750 1590 1400 1240 1080 914 813 673 529 409 303
*5
1
/2” (140 mm) Centers
**9
1
/2” (241 mm) Centers
All two tier and 24T high ratings not IBR approved.
Dimensions in bold indicate metric units.
NOTE: Rating is Btu/hr/ft (Watts/meter) of finned length (for element dimensions see page 49). Hot water ratings determined by applying correction factor to steam ratings, are for
water velocities of 3 ft/sec (.91 m/s) or greater. See page 9, Chart S-1 for correction factors for water velocities other than 3 ft/sec (.91 m/s). For definition of installed height and heating
effect factors, see page 11. For heating ratings at other steam pressures and/or entering air temperatures, see page 10, Table S-2.