Trane FIN-PRC004 Air Conditioner User Manual


 
FIN-PRC004-EN78
Performance
Data Security Wall Fin
Table PD-2 Copper/Aluminum Elements Watts/Meter
Steam
Rating Hot Water (Ave.)
Copper/Aluminum Elements with Partially Perforated Enclosures 102°C 104°C99°C93°C88°C82°C77°C71°C66°C60°C54°C
Tube Fin Size Fins/ Encl. Tiers & Mtg. Height Factor Factor
Size Inches Foot Type Centers Inches 1.00 1.05 0.95 0.86 0.78 0.69 0.61 0.53 0.45 0.40 0.33
S12-SP 1 406 1260 1330 1200 1090 980 870 770 660 570 500 410
S18-SP 1 559 1490 1570 1420 1280 1160 1030 910 790 670 600 490
19 mm 108 x 92 131 S18-SP 2-152 mm 559 2180 2300 2080 1870 1700 1510 1330 1150 980 870 720
F12-SP 1 406 1150 1210 1100 990 890 800 700 620 520 460 380
F18-SP 1 559 1350 1410 1280 1150 1050 930 820 710 610 540 440
F18-SP 2-152 mm 559 2000 2110 1900 1720 1560 1380 1220 1060 900 800 660
S12-SP 1 406 1370 1440 1310 1180 1080 950 840 730 620 550 450
S18-SP 1 559 *1720 1810 1630 1480 1350 1190 1050 910 780 690 590
19 mm 108 x 92 164 S18-SP 2-152 mm 559 2310 2420 2190 1980 1800 1600 1400 1220 1040 920 760
F12-SP 1 406 1300 1360 1230 1120 1010 890 790 690 590 520 430
F18-SP 1 559 1550 1620 1470 1330 1210 1070 940 820 690 620 510
F18-SP 2-152 mm 559 2200 2310 2100 1890 1720 1520 1350 1160 990 880 730
S12-SP 1 406 1430 1500 1370 1230 1120 990 870 760 640 580 470
S18-SP 1 559 1660 1750 1580 1430 1300 1140 1020 880 750 660 550
25 mm 108 x 108 131 S18-SP 2-152 mm 559 2300 2410 2180 1980 1790 1590 1400 1220 1040 920 760
F12-SP 1 406 1310 1370 1240 1120 1020 900 800 690 590 520 430
F18-SP 1 559 1490 1570 1410 1280 1160 1030 910 790 670 600 490
F18-SP 2-152 mm 559 2200 2310 2100 1890 1720 1520 1350 1160 990 880 730
S12-SP 1 406 1510 1590 1430 1300 1170 1040 920 800 680 610 500
S18-SP 1 559 1900 2000 1810 1630 1480 1320 1160 1010 860 760 620
25 mm 108 x 108 164 S18-SP 2-152 mm 559 2170 2280 2070 1860 1690 1500 1330 1150 980 870 720
F12-SP 1 406 1410 1480 1350 1210 1110 970 870 750 630 570 460
F18-SP 1 559 1700 1790 1610 1460 1330 1170 1040 900 770 680 560
F18-SP 2-152 mm 559 2070 2170 1960 1780 1610 1420 1260 1100 930 830 680
S12-SP 1 406 1410 1480 1350 1210 1110 970 870 750 630 570 460
S18-SP 1 559 1630 1720 1560 1400 1280 1120 1000 870 740 650 540
32 mm 108 x 108 131 S18-SP 2-152 mm 559 *2260 2370 2140 1940 1760 1560 1370 1200 1020 900 750
F12-SP 1 406 1290 1360 1220 1110 1010 880 790 680 580 520 420
F18-SP 1 559 1470 1550 1390 1270 1140 1020 890 780 660 590 480
F18-SP 2-152 mm 559 2160 2270 2060 1860 1690 1490 1320 1140 970 870 710
S12-SP 1 406 *1480 1560 1400 1270 1150 1020 900 790 660 600 490
S18-SP 1 559 *1860 1960 1760 1610 1450 1290 1130 990 840 750 620
32 mm 108 x 108 164 S18-SP 2-152 mm 559 2130 2240 2030 1840 1660 1470 1300 1130 960 860 700
F12-SP 1 406 1390 1460 1330 1200 1090 960 850 740 620 560 460
F18-SP 1 559 1670 1760 1590 1440 1310 1150 1020 880 750 670 550
F18-SP 2-152 mm 559 2030 2130 1920 1740 1590 1400 1240 1080 910 810 670
1. *I = B = R Rating on Assemblies as marked.
2. Mounting Height is the dimension from the floor to the top of the enclosure to obtain listed capacities.
3. Two-tier applications can only be used with 457 mm high enclosures installed on 152 mm center lines.