Performance
Data
Table PD-4 Ratings 4 (102 mm) Deep, Type S - Enclosure With Copper/Aluminum Elements
Steam Capacity Hot Water Capacity
Per Ft.-1 Psi at 65°F Air Btu/Hr./Ft. At 65°F Air, Average Water Temperature
Per Meter - 6.895 kPa Watts/Meter At 18.3°C Air, Average Water Temperature
at 18.3°C Air
Install. 220°F 210°F 200°F 190°F 180°F 170°F 160°F 150°F140°F130°F120°F 110°F 100°F
Fin Series Height EDR 104°C99°C93°C88°C82°C77°C71°C66°C60°C54°C49°C43°C38°C
Per Foot Inches Sq. Ft. Btu/Hr./Ft. IBR Factor Steam to Hot Water
Element Per Meter Tiers Encl. mm Sq. M Watts/Meter 1.05 0.95 0.86 0.78 0.69 0.61 0.53 0.45 0.40 0.33 0.26 0.20 0.15
10S 12
1
/8 4.45 10.70 1125 1015 920 835 740 650 565 480 430 355 280 215 160
308 48 1030 1080 976 885 803 712 625 543 462 413 341 269 207 154
14S 16
1
/8 4.62 1110 1165 1055 955 865 765 675 590 500 445 365 290 220 165
410 50 1070 1120 1010 918 832 736 649 567 481 428 351 279 212 159
1 18S 20
1
/8 4.70 1130 1185 1075` 970 880 780 690 600 510 450 370 295 225 170
511 51 1090 1140 1030 933 846 750 664 577 490 433 356 284 216 163
24S 26
1
/8 4.87 1170 1230 1110 1005 910 805 715 620 525 470 385 305 235 175
664 52 1120 1180 1070 966 875 774 688 596 505 452 370 293 226 168
3
/4 CA 40 2* 14S 16
1
/8 7.04 1690 1775 1605 1455 1320 1165 1030 895 760 675 555 440 340 255
19 mm 131 m 410 76 1620 1710 1540 1400 1270 1120 990 861 731 649 534 423 327 245
Copper Tube 18S 20
1
/8 7.62 1830 1920 1740 1575 1425 1260 1115 970 825 730 605 475 365 275
Alum. Fins 511 82 1760 1850 1670 1520 1370 1210 1070 933 793 702 582 457 351 264
Fins 3
1
/4 x 3
1
/4 2** 24S 26
1
/8 8.04 1930 2025 1835 1660 1505 1330 1175 1025 870 770 635 500 385 290
83 x 83 mm 664 87 1860 1950 1760 1600 1450 1280 1130 986 837 740 611 481 370 279
Thickness .0135 10S 12
1
/8 5.16 1240 1300 1180 1065 965 855 755 655 560 495 410 320 250 185
.34 mm 308 56 1190 1250 1140 1020 928 822 726 630 538 476 394 308 240 178
14S 16
1
/8 5.58 1340 1405 1275 1150 1045 925 815 710 605 535 440 350 270 200
410 60 1290 1350 1230 1110 1000 889 784 683 582 514 423 337 260 192
1 18S 20
1
/8 5.95 1430 1500 1360 1230 1115 985 870 760 645 570 470 370 285 215
511 64 1380 1440 1310 1180 1070 947 837 731 620 548 452 356 274 207
24S 26
1
/8 6.29 1510 1585 1435 1300 1180 1040 920 800 680 605 500 390 300 225
664 68 1450 1520 1380 1250 1140 1000 885 769 654 582 481 375 288 216
50 2* 14S 16
1
/8 7.33 1760 1850 1670 1515 1370 1215 1075 930 790 705 580 460 350 265
164 m 410 79 1690 1780 1610 1460 1320 1170 1030 894 760 678 558 442 337 255
18S 20
1
/8 8.33 2000 2100 1900 1720 1560 1380 1220 1060 900 800 660 520 400 300
511 90 1920 2020 1830 1650 1500 1330 1170 1020 865 769 635 500 385 288
2** 24S 26
1
/8 8.95 2150 2260 2040 1850 1675 1485 1310 1140 965 860 710 560 430 320
664 96 2070 2170 1960 1780 1610 1430 1260 1100 928 827 683 538 413 308
10S 12
1
/8 5.54 1330 1395 1265 1145 1035 920 810 705 600 530 440 345 265 200
308 60 1280 1340 1220 1100 995 885 779 678 577 510 423 332 255 192
14S 16
1
/8 6.08 1460 1535 1385 1255 1140 1005 890 730 655 585 480 380 290 220
410 65 1400 1480 1330 1210 1100 966 856 702 630 563 462 365 279 212
1 18S 20
1
/8 6.58 1580 1660 1500 1360 1230 1090 965 835 710 630 520 410 315 235
511 71 1520 1600 1440 1310 1180 1050 928 803 683 606 500 394 303 226
24S 26
1
/8 7.08 1700 1785 1615 1460 1325 1175 1035 900 765 680 560 440 340 255
664 76 1640 1720 1550 1400 1270 1130 995 865 736 654 538 423 327 245
58 2* 14S 16
1
/8 7.45 1790 1880 1700 1540 1395 1235 1090 950 805 715 590 465 360 270
190 m 410 80 1720 1810 1640 1480 1340 1190 1050 914 774 688 567 447 346 260
18S 20
1
/8 8.70 2090 2195 1985 1795 1630 1440 1275 1105 904 835 690 545 420 315
511 94 2010 2110 1910 1730 1570 1380 1230 1060 869 803 664 524 404 303
2** 24S 26
1
/8 9.58 2300 2415 2185 1980 1795 1585 1405 1220 1035 920 760 600 460 345
664 103 2210 2320 2100 1900 1730 1520 1350 1170 995 885 731 577 442 332
*5
1
/2 (140 mm) Centers
**9
1
/2 (241 mm) Centers
24 (610 mm) High ratings not IBR approved.
Dimensions in bold indicate metric units.
Sloping
Top
NOTE: Rating is Btu/hr/ft (Watts/meter) of finned length (for element dimensions see page 49). Hot water ratings determined by applying correction factor to steam ratings, are for
water velocities of 3 ft/sec (.91 m/s) or greater. See page 9, Chart S-1 for correction factors for water velocities other than 3 ft/sec (.91 m/s). For definition of installed height and heating
effect factors, see page 11. For heating ratings at other steam pressures and/or entering air temperatures, see page 10, Table S-2.