Installation
CAH-SVX01A-EN 27
Bag or Cartridge Filters.
1 Disconnect power to the unit.
2 Keeping the bag filters folded,
slide each filter into the filter
rack, pushing them tightly
against the unit. Pleats should be
in the vertical position.
3 If using optional pre-filters, slide
them into the appropriate filter
rack.
4 If block-offs are provided with the
unit, slide the block-offs into the
filter track.
5 Close and secure the access
door, making certain the door
closes snug against the rack.
Note: The block-off is intended to
make a seal when the access door is
closed. It may require a few
adjustments to ensure a proper seal.
Figure 25. Filter block-off placement
Outdoor Unit Weather
Hood(s)
1 Per the unit drawing determine
mounting location of the unit
weather hoods.
2 All weather hoods have been
pre-fit on the unit and removed
for separate shipping at the
factory. Remove any factory
mounted screws located in the
weather hood mounting
location.
3 Using the factory provided
screws mount the weather hoods
to the unit.
Note: Note it is required that the
hoods be sealed to the unit using
field provided caulk or gasket.