Installation
CAH-SVX01A-EN 19
Insert field provided threaded
rods through the bottom lifting
lug and shipping split plates on
each sides of the unit. Draw both
sides of the section together
equally to prevent damage and
distortion of the sections as they
joined. Do not try to join sections
by tightening only one side of
the rods (see Figure 13).
Note: Field-provided threaded
hardware should consist of 5/8-11x12
inch threaded rods 5/8-inch lock
washers and 5/8-inch nuts.
Note: Failure to compress the butyl
tape may result in air and water
leakage.
Once the sections are pulled
together, add a bead of caulk
(sikaflex) along the seam
between the two perimeter caps
(see Figure 14).
Install the assembly hardware as
applicable for the shipping split
frame inside of unit, the walls,
and the roof as demonstrated in
the following assembly sections.
Figure 13. Insert field provided threaded rods
Figure 14. Add caulk along the seam