Trane Custom Climate Changer Air Handlers Air Cleaner User Manual


 
Installation
CAH-SVX01A-EN 17
TCC Model
Assembly
Instructions
If your nameplate model number
begins with TCC, use the assembly
instructions below.
Joining sections - Edge to
Edge
Units must be installed level for
proper drainage of condensate from
the drain pan and for squareness of
the sections during installation. In
addition, each section in a multi-
section unit must be properly
supported.
Note: Leveling each section,
beginning with the first section, is
critical. Failure to level and align the
sections immediately creates greater
misalignment or even structural
damage afterward.
Remove all wooden blocks under
the unit and shipping protection
from adjoining surfaces (see
Figure 9).
Place the first section of the air
handler on the end of the roof
curb or the housekeeping pad.
The section must be level from
side-to-side and front to back.
Section squareness should be
within 1/8-inch. Remove the
bottom bolts from lifting lugs
located at the shipping split (see
Figure 10).
Figure 9. Remove shipping blocks
Figure 10. Remove lifting lug bolts