Toshiba RAS-15LAV-UL Air Conditioner User Manual


 
7-2. O
p
eration Data
<Coolin
g
>
Tempeature Model name Standard Heat exchanger Indoor Outdoor Compressor
condition [°F (°C)]
RAS- pressure pipe temp. fan mode fan mode revolution
Indoor Outdoor P [psi (MPa)] T1 [°F (°C)] T2 [°F (°C)] (rps)
80/67 98/75 131 to 160 52 to 55 40 to 42
(26.7/19.4) (35/23.9) (0.9 to 1.1) (11 to 13) (37 to 39)
131 to 160 52 to 55 40 to 42
(0.9 to 1.1) (11 to 13) (42 to 44)
<Heating>
Tempeature Model name Standard Heat exchanger Indoor Outdoor Compressor
RAS- pressure pipe temp. fan mode fan mode revolution
Indoor Outdoor (rps)
70/60 47/43 363 to 392 102 to 105 32 to 37
(21.1/15.6) (8.3/6.1) (2.5 to 2.7) (39 to 41) (0 to 3)
377 to 406 106 to 106 32 to 36
(2.6 to 2.8) (41 to 43) (0 to 2)
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchaner path U bent.
(Thermistor themometer)
2. Connecting piping condition : 25 ft (7.5m)
74
High High 82
15LKV-UL
17LKV-UL
High High
17LKV-UL High High 62
High High 5715LKV-UL
131 to 160 52 to 55 41 to 43
(0.9 to 1.1) (11 to 13) (42 to 44)
22LKV-UL High High 88
116 to 145 52 to 55 104 to 107
(0.8 to 1.0) (11 to 13) (42 to 44)
22LKV-UL High High 84
FILE NO. SVM-10020
23
condition [°F (°C)]
P [psi (MPa)]
T1 [°F (°C)] T2 [°F (°C)]