Samson 5476 Heating System User Manual


 
FB Function WE Anl Comments
36
(12)
to
43
(19)
BE8
to
BE1
All FB36 to 43 = ON: Binary input in error status register
Select: StEIG: Fault indicated by rising edge/make contact
FALL: Fault indicated by negative edge/break contact
44
(20)
Modem operation OFF All Select: 8-bit: 8-bit addressing
16-bit: 16-bit addressing
FB44 = ON: Modem function activated
Function block parameters:
Cyclical initialization In/0to255min(30min)
Intervals between dialing PA/0to255 min (5 min)
Modem timeout t
0
/ 0 to 99 min (5 min)
Dialing procedure/ PULS/ton (PULS)
Phone number of station GLT / 0 to 9, P, -; max. 23 characters
Setting only possible after entering key number!
45
(21)
Dial-up also upon
corrected fault
OFF All FB45 = ON: Dial-up when faults exist/remedied
FB45 = OFF: Dial up only when faults exist
Setting only possible after entering key number!
46
(22)
Phone number of
alternative recipient
OFF All FB46 = ON: Dialing an alternative recipient
Function block parameters:
Number of dialing attempts An / 0 to 99 (5)
Phone number of alternative recipient/0to9,P,-;max. 23 char.
Setting only possible after entering key number!
47
(23)
Fault alarm output
BA8
OFF All FB47 = ON and FSr > 0: BA8 = ON
Pump management for UP1 no longer available
Setting only possible after entering key number!
FB Function block, WE Default setting, Anl System code number
86 EB 5476 EN
Appendix