Samson 5476 Heating System User Manual


 
If you wish to use more than 32 devices in line or need to bridge greater distances, make sure
repeaters (e.g. TROVIS 5482) are installed to replicate the signal. With 8-bit addressing, a
maximum of 246 devices can be addressed and connected to a bus.
Warning!
You are required to follow the relevant standards and regulations concerning lightning and
overvoltage protection on installation.
Function
WE Configuration
Modem operation OFF
8 bit
FB44 = OFF
8 bit/16 bit
Parameters*
WE Range of values
Station address 255 1 to 247 ( 8 bit)
1 to 999 (16 bit)
Baud rate 9600 150 to 9600
* –> Section 9.3 (”Description of communication parameters to be adjusted“)
9.3 Description of communication parameters to be adjusted
Station address (ST.-NO)
This address is used to identify the controller in bus or modem mode. In a system, each control-
ler needs to be assigned a unique address.
Baud rate (BAUD)
In a bus system, baud rate refers to the transfer speed between control system and controller. In
modem mode, baud rate refers to the transfer speed between controller and modem.
The baud rate adjusted at the controller must correspond with the baud rate of the control sys
-
tem, otherwise no communication can be established.
Cyclical initialization (In)
This parameter defines the period of time for a cyclical issue of the initialization command
“ATZ“. The command is not issued during dial-up or when connected. “ATZ“ causes the pro
-
file 0 to be copied to the active profile, provided the modem parameters have been set and
saved in profile 0 using a suitable terminal program.
Dialing pause to the control station (PA)
It is recommendable to pause for approx. 3 to 5 minutes between dialing up to the control sys
-
tem to avoid apermanent overloading of the telecommunications network.The
Dialing pause to
the control station
defines the interval between 2 dialing attempts.
EB 5476 EN 69