Quadra-Fire QFP44 Stove User Manual


 
Quadra-Fire • QFP44 • 4051-300 Rev M • 09/08 45
INTERIOR
Heat Shield or
Extended
Heat Shield
Wall Shield
Firestop
Heat Shield
1-1/2 in. (38 mm) min.
overlap
SHEATHING
Slip Section
can be extended
Inner Vent
Outer Vent
EXTERIOR
Figure 10.20 Venting through the wall
Note: When using termination caps with factory-supplied
heat shield attached, no additional wall shield  restop is
required on the exterior side of a combustible wall.
J. Install Horizontal Termination Cap
WARNING! Risk of Fire! The telescoping À ue section
of the termination cap MUST be used when connecting
vent.
1-1/2 (38 mm) minimum overlap of À ue telescoping
section is required.
Failure to maintain overlap may cause overheating and
¿ re.
Vent termination must not be recessed in the wall. Siding
may be brought to the edge of the cap base.
Flash and seal as appropriate for siding material at
outside edges of cap.
When installing a horizontal termination cap, follow
the cap location guidelines as prescribed by current
ANSI Z223.1 and CAN/CGA-B149 installation codes
and refer to Section 6 of this manual.
CAUTION! Risk of Burns! Local codes may require
installation of a cap shield to prevent anything or anyone
from touching the hot cap.
NOTICE: For certain exposures which require superior
resistance to wind-driven rain penetration, a À ashing kit and
HPC caps are available. When penetrating a brick wall, a
brick extension kit is available for framing the brick.