Quadra-Fire QFP44 Stove User Manual


 
Quadra-Fire • QFP44 • 4051-300 Rev M • 09/08 35
C. Install the Ceiling Firestop
A ceiling  restop MUST be used between  oors and at-
tics.
Frame an opening 10 in. by 10 in. (254 mm by 254
mm) whenever the vent penetrates a ceiling/ oor (see
Figure 8.3).
Frame the area with the same sized lumber as used in
ceiling/ oor joist.
The ceiling  restop may be installed above or below
the ceiling joists when installed with a attic insulation
shield. It must be under joists between  oors that are
not insulated. Refer to Figure 8.4.
Secure with three fasteners on each side.
WARNING! Risk of Fire! DO NOT pack insulation around
the vent. Insulation must be kept back from the pipe to pre-
vent overheating.
Figure 8.3 Installing Ceiling Firestop
Figure 8.4 Installing the Attic Shield
Attic Above
10 in. (254 mm)
Hole should measure
10 in. x 10 in.
(254 mm x 254 mm)
inside to inside
10 in.
(254 mm)
3 fasteners
per side
Ceiling firestop
installed below ceiling.
Ceiling firestop
installed above ceiling.
Install attic insula-
tion shields before
or after installation
of vent system.