Honeywell XL 800 SERIES Smoke Alarm User Manual


 
Excel 800 Wiring
5 EN1B-0410GE51 R0908A
XL800 Series Power Consumption
When selecting the appropriate power supply, the power
consumption of the XL800 modules must be taken into
account.
Table 3. XL800 power consumption
max. power consumption
model 24 Vac, 60 Hz 24 Vdc
XCL8010AU with
watchdog load
690 mA 640 mA
XCL8010AU without
watchdog load
190 mA 140 mA
XF821AU, XFL821AU 130 mA 80 mA
XF822AU, XFR822AU,
XFL822AU, XFLR822AU
160 mA 90 mA
XF823AU, XFL823AU 180 mA 130 mA
XF824AU, XFR824AU,
XFL824AU, XFLR824AU
140 mA 90 mA
XFR825AU 140 mA 90 mA
I/O Modules
Variants of I/O Modules
There are two variants of I/O modules:
Panel Bus I/O modules with communication via Panel Bus
(light-gray housings)
Modules are automatically commissioned (with firmware
download) by the XCL8010AU
L
ONWORKS Bus I/O modules (dark-gray housings) with
communication via L
ONWORKS (FTT10-A, link power
compatible) for easy integration and use with 3
rd
-party
controllers
Terminal Sockets
I/O modules are mounted on the appropriate terminal
sockets. Panel Bus I/O modules and L
ONWORKS Bus I/O
modules use the same terminal sockets.
Color Coding
To distinguish modules and components, the following color
coding is used:
Table 4. Color coding of Excel 800 Modules
color part
red All of the user-accessible adjustable
mechanical parts (i.e., bridge connectors and
locking mechanism) and operating controls
(manual overrides, etc.)
light-gray
Panel Bus I/O modules
dark-gray
L
ONWORKS Bus I/O modules