I/O Modules Troubleshooting
Check if the power supply voltage level is OK and that there is no high voltage (> 24 VAC or > 40 VDC) connected to the
inputs/outputs of the XF821AU, XFL821AU, XF822AU, XFL822AU, XFR822AU, XFLR822AU, XF823AU, and XFL823AU I/O
modules.
Replace the problem I/O module with another module of the same kind.
If the problem persists, this is an indication that the problem is caused by the application or incorrect wiring.
If the problem is solved, this is an indication that the I/O module was defective.
For troubleshooting purposes on all I/O modules the following features can be used:
Power LED
Service LED
Service button
In addition, a module-specific troubleshooting may be necessary.
Power LED of I/O Modules
Table 42. Power LED of I/O modules
case power LED meaning remedy
1 ON
I/O module is powered
No action necessary
2 OFF
No power
Check power supply
3 Flashing continuously
If the I/O module’s service LED is likewise
flashing, the I/O module is in the boot mode
Wait until rebooting (firmware
download) has been completed