Honeywell XL 800 SERIES Smoke Alarm User Manual


 
Excel 800 Troubleshooting
33 EN1B-0410GE51 R0908A
Table 39. XCL8010AU L
ONWORKS service LED
case When can it occur? meaning remedy
1
Anytime
Node is configured and running normally
No action necessary
2
Power up of controller
Bad node hardware
Replace hardware
3
Power up of controller
Bad node hardware
Replace hardware
4
Power up / reset
Node lacks application.
May be caused by neuron chip firmware when
a mismatch occurs on application checksum
Using EXCELON, set module to
“configured online”
If problem persists, the MIP software
on LW interface has been erased due
to wrong setting performed using
ECHELON tool:
Replace hardware
5
Anytime
Watchdog timer resets occurring.
Possible corrupt EEPROM and bootstrap
mode
Download firmware
6
Anytime
Node is unconfigured but has an application
Proceed with commissioning
C-Bus Tx and Rx LEDs
Table 40. XCL8010AU C-Bus Tx and Rx LEDs
case C-Bus LEDs meaning remedy
If the C-bus is functioning properly, then the
XCL8010AU is functioning properly
No action necessary
1
Both LEDs are flashing
If the C-bus is not functioning properly, then
the termination can be wrong
Check C-bus termination switch S1
(location: see Fig. 4 on page 7)
2
Both LEDs are OFF
No C-bus communication
Check C-bus settings
3 Both LEDs are flashing
synchronously
No C-bus communication
Check C-bus wiring
HMI Tx and Rx LEDs
Table 41. XCL8010AU HMI Tx and Rx LEDs
case HMI LEDs meaning remedy
1
Both LEDs are flashing
If the HMI Interface is functioning properly,
then the XCL8010AU is functioning properly
No action necessary
2
Both LEDs are OFF
No HMI Interface communication
Check HMI Interface connection and
proper earthing of connected
hardware