Honeywell XL 800 SERIES Smoke Alarm User Manual


 
Mounting/Dismounting Modules Excel 800
EN1B-0410GE51 R0908A
18
Connecting Laptops (XL-Online/CARE)
Connect a laptop (on which e.g., XL-Online or CARE has
been installed) to the HMI interface or L
ONWORKS interface
of the XCL8010AU
Controller Module by means of
the XW885 cable or
the XW585 cable connected with an XW586 Cable.
XCL8010AU Terminals
74
14
10 7
2
3
4
78
73
13
9 6
1
77
72
12
8 5
76
71
11
75
24
V~
24
V~
24
V~
24
V~ 0
LON
2
C- C-
C+ C+
LON
2
LON
1
LON
1
24
V~ 0
24
V~ 0
NC
24
V~0
COM
B
COM
B
COM
A
COM
A
SHIELD SHIELD
87 6
5
4 32 1
*
*Watch Dog
Relay
Fig. 26. Terminal assignment and internal connections of
the XCL8010AU Controller Module
Table 12. Description of XCL8010AU terminals
ter-
minal
signal comment
71, 75 COM a
2-wire communication bus
(LON/Panel Bus)
72, 76 COM b
2-wire communication bus
(LON/Panel Bus)
73, 77 24 V~ Power supply for I/O modules
74, 78 24 V~0 Power supply for I/O modules
1 24 V~ Power supply from transformer
2 24 V~0 Power supply from transformer
3 24 V~0 Alarm/watchdog output
4 NC Alarm/watchdog output
5, 8 C+ C-Bus
6, 9 C- C-Bus
7, 10 Shield C-Bus shield
11, 12 LON LONWORKS IN
13, 14 LON LONWORKS OUT
Features
LONWORKS Interface and Terminals
The XCL8010AU Controller Module features
An RJ45 socket serving as an interface
to connect laptops or HMIs to the L
ONWORKS Bus
LONWORKS terminals 11, 12, 13, and 14
to connect L
ONWORKS Bus I/O modules or other
L
ONWORKS devices to the XCL8010AU Controller or other
L
ONWORKS controllers.
Fig. 27. L
ONWORKS interface and LONWORKS terminals
LONWORKS Interface Signals on RJ45 Socket
Table 13. Signals of L
ONWORKS interface
pin signal type
1 Connection to LONWORKS Bus
2 Connection to LONWORKS Bus
3 8 Not used
LONWORKS Service LED and Button
The XCL8010AU Controller Module is equipped with a
L
ONWORKS service button and corresponding LONWORKS
Service LED (status: yellow/OFF).
1
LON
2
Fig. 28. L
ONWORKS service button (1) and service LED (2)
See also section "Troubleshooting" on page 31.