Troubleshooting
Testing Wiring Connections
The push-in terminals feature small holes (1 mm in diameter)
which can be used to measure the signals.
Insert a probe (1) as shown on the right.
Fig. 49. Testing wiring connections
Troubleshooting on the XCL8010AU Controller
The following LEDs of the XCL8010AU Controller can be used for troubleshooting purposes:
Power LED (green)
Alarm LED (red)
L
ONWORKS service LED
C-Bus Tx and Rx LEDs
HMI Tx and Rx LEDs
Power LED (green)
Table 37. XCL8010AU power LED
case power LED meaning remedy
1 ON
Normal operation No action necessary
2 Flashing
One or more of the internal voltage supplies
are outside of the permissible ranges. The
controller stops operation.
Check power
Check wiring
If problem persists, replace hardware
3 Goes out briefly
The operator has activated the reset button
The controller is performing a warm start
No action necessary