Heatiator Rave4013i-c Indoor Fireplace User Manual


 
Heatilator • RAVE4013I-C • 2293-900 Rev. C • 8/1236
C. Install the Ceiling Firestop
A ceiling restop MUST be used between
oors and attics.
SLP pipe only - Frame opening 9 in. x
9 in. (229 mm x 229 mm) whenever the
vent penetrates a ceiling/floor (see Figure
8.4).
• Frame the area with the same sized lumber
as used in ceiling/ oor joist.
• The ceiling restop may be installed above or
below the ceiling joists when installed with a
attic insulation shield. It must be under joists
between oors that are not insulated. Refer
to Figure 8.5.
• Secure with three fasteners on each side.
WARNING! Risk of Fire! DO NOT pack insu-
lation around the vent. Insulation must be kept
back from the pipe to prevent overheating.
Figure 8.4 Installing Ceiling Firestop
ATTIC ABOVE
A
PIPE
SLP
A
9 in. (229 mm)
A
Figure 8.5 Installing the Attic Shield
3 FASTENERS
PER SIDE
INSTALL ATTIC INSULATION SHIELDS
BEFORE OR AFTER INSTALLATION OF VENT SYSTEM
CEILING FIRESTOP
INSTALLED BELOW CEILING
CEILING FIRESTOP
INSTALLED ABOVE CEILING