Heatiator Rave4013i-c Indoor Fireplace User Manual


 
27Heatilator • RAVE4013I-C • 2293-900 Rev. C • 8/12
H
2
H
1
V
2
V
1
Top Vent - Horizontal Termination
Venting with 3 elbows
Note: Use SLP Series
components only.
1. Top Vent - Horizontal Termination - (continued)
Figure 7.6
RAVE4013I-C
V
1
Minimum H
1
+ H
2
Maximum V
2
V
1
+ V
2
Minimum
90° Elbow 6 ft. 1.8 m * *
1 ft. 305 mm 10 ft. 3.0 m * *
2 ft. 610 mm 12 ft. 3.7 m * *
3 ft. 914 mm 14 ft. 4.3 m * *
H
1
+ H
2
MAX. =14 ft. (4.3 m)
V
1
+ V
2
+ H
1
+ H
2
MAX. = 40 ft. (12.2 m)
*No speci c restrictions on this value EXCEPT V
1
+ V
2
+ H cannot exceed 40 ft. (12.2 m)
Note: There MUST be a 25%
reduction in total H when using
ex vent except when using the
simple up and out installation
(see Figure 7.3).
CAUTION: The SLP-HRC-SS and SLP-HRC-ZC-SS
termination caps are not approved for use with pro-
pane (LP) fuel. May lead to elevated glass temper-
ature that may cause tempered glass breakage.