Heatiator Rave4013i-c Indoor Fireplace User Manual


 
Heatilator • RAVE4013I-C • 2293-900 Rev. C • 8/1228
Figure 7.7
1. Top Vent - Horizontal Termination - (continued)
Top Vent - Horizontal Termination
Venting with 3 elbows
Note: Use SLP Series
components only.
V Minimum
H
1
+ H
2
+ H
3
MAXIMUM
RAVE4013I-C (NG ONLY)
3 ft. 914 mm 15 ft. 4.6 m
H
1
+ H
2
+ H
3
MAX. = 15 ft. (4.6 m)
V
1
MAX. = 7 ft (2.1 m)
V
1
H
1
H
3
H
2
INSTALLED
HORIZONTALLY
INSTALLED
HORIZONTALLY
Note: There MUST be a 25%
reduction in total H when using
ex vent except when using the
simple up and out installation
(see Figure 7.3).
CAUTION: The SLP-HRC-SS and SLP-HRC-ZC-SS
termination caps are not approved for use with pro-
pane (LP) fuel. May lead to elevated glass temper-
ature that may cause tempered glass breakage.