Heatiator Rave4013i-c Indoor Fireplace User Manual


 
Heatilator • RAVE4013I-C • 2293-900 Rev. C • 8/1232
Top Vent - Vertical Termination
Venting with 4 elbows
Note: Use SLP Series
components only.
Note: There MUST be a 25%
reduction in total H when using
ex vent except when using the
simple up and out installation
(see Figure 5.3).
V
1
MIN. H
1
MAX. V
2
MIN. H
2
MAX. V
3
MIN.
1-1/2 ft. 457 mm 4 ft. 1.2 m 4 ft. 1.2 m 4 ft. 1.2 m 3-1/2 ft. 1.0 m
V
1
+ V
2
+ V
3 +
H
1
+ H
2
Maximum= 40 ft. (12.2 m)
Figure 7.13
V
1
H
1
V
2
V
3
H
2