Heatiator BH60 Boiler User Manual


 
38

1. No pellets in hopper.
2. Firebox draft may be too low for low draft pressure
switch in feeder circuit to operate.  
  , loose or missing
gasket on doors or hopper lid, or a faulty pressure
switch.
3. Feed motor will not run until the ESP senses 170
deg. F. Maybe you did not put enough pellets in
the burn pot before lighting the re manually.
4. Something is restricting ow in the hopper or
causing the slide plate to stick.
5. Feed motor has failed.

1. Feed rate too high.
2. Draft too low. (Check burn pot clean-out slide and
door gasket).
3. Burn pot or heat exchanger tubes may need to
be cleaned.
4. Combination of all the above.
5. A 6 blink control board status
indication is caused by poor or incomplete
combustion. The Automatic Ignition circuit board
has the ability to track the combustion through
feed settings and ESP temperatures. When the
control board has calculated poor or incomplete
combustion, it will shut down the unit as a safety
feature. (Poor or incomplete combustion is
a contributor of creosote which may cause a
chimney re)

1. Blocked or partially blocked ue.
2. Blocked or partially blocked inlet air.
a. Backdraft damper on the inlet pipe may be stuck
closed.
b. If outside air is installed, the inlet cover may be
blocked.
3. The air chamber under the burnpot may be lled
with nes and small bits of ash.
4. The holes in the burnpot may be getting lled with
ash or carbon buildup.
5. Combustion blower fan may need cleaned.
6. There is no fuel in the hopper.

Seal the vent pipe joints and connection to unit with
silicone.

1. No pellets in hopper.
2. Draft setting is too low.
3. Something is restricting fuel ow.
4. Feed motor or combustion blower has failed.
5. Power failure or blown fuse.
6. Firebox door or hopper left open.

1. Air-fuel ratio is too rich.
A. Feed rate too high.
B. Draft too low caused by a gasket leak.

1. Feed rate too low
2. Draft too low because of gasket leak.
3. Poor quality or damp pellets
4. Combination of 1 and 2.

Whenever your boiler is not burning, take the
opportunity to scrape the burn pot to remove carbon
buildup. A vacuum cleaner is handy to remove the
residue.        

Carbon buildup can be scraped loose with the re
burning using the special tool provided with your boiler.
Scrape the oor and sides of the burn pot. The carbon
will be pushed out by the incoming fuel. Always wear
gloves to do this.

Ashes can be removed while in operation, but extra
care must be taken and always wear gloves.
Maximum Feed Adjuster settings are not needed
in most cases. Operating in the normal range (#4)
is recommended when maximum heat output is not
required. The ESP prevents the stove from being over-
red.
Keep the boiler free of dust and dirt.

Pellet fuels are put into 3 categories in terms of ash
content. Premium at 1% or less, Standard at 3% or
less and all others at 3% or more.
The BH60 is capable of burning all 3 categories
of pellets, due to a patented feeder and burn pot
system.
It should be noted, however, that higher ash content
will require more frequent ash removal, scraping of
the burn pot, and may provide less BTU’s per pound.
Normally, standard and high ash pellets cost less
than premium pellets and can be cost effective when
burned in the BH60.
The moisture content must not exceed 8%. Higher
moisture will rob BTU’s and may not burn properly.

