Goodman Mfg SS-CPC90-150 Air Conditioner User Manual


 
prodUCt speCifiCations
prodUCt speCifiCations
SS-CPC90-150 www.goodmanmfg.com 9
airflow data — 10 tons

ESP


0 1 2 3 4 5
 RPM BHP  RPM BHP  RPM BHP  RPM BHP  RPM BHP  RPM BHP
0.2 4632 781 1.76 4203 742 1.41 3927 691 1.17 3510 658 0.9
0.4 4488 825 1.85 4183 783 1.54 3733 748 1.23 3512 693 1
0.6 4442 880 2.02 4066 830 1.63 3717 786 1.31
0.8 4001 885 1.77 3622 835 1.41
1 3603 890 1.55
1.2

ESP


0 1 2 3 4 5
 RPM BHP  RPM BHP  RPM BHP  RPM BHP  RPM BHP  RPM BHP
0.8 4435 940 2.22 4078 886 1.82
1 4462 997 2.47 4103 945 2.05 3539 892 1.52
1.2 4513 1054 2.75 4127 1003 2.26 3568 950 1.71
1.4 4126 1064 2.52 3597 1008 1.92
1.6 4438 1116 2.97 3759 1069 2.25
1.8 3956 1124 2.55
2 4050 1179 3.05 3473 1132 2.32

ESP


0 1 2 3 4 5
 RPM BHP  RPM BHP  RPM BHP  RPM BHP  RPM BHP  RPM BHP
0.2 4562 736 1.58 4253 691 1.29 3893 642 1
0.4 4497 780 1.7 4200 736 1.41 3735 691 1.06 3322 648 0.83
0.6 4467 824 1.81 4221 784 1.55 3689 741 1.18
0.8 4564 873 2.06 4170 830 1.68 3677 785 1.29
1 4129 875 1.81 3498 835 1.34
1.2 3558 879 1.49

ESP


0 1 2 3 4 5
 RPM BHP  RPM BHP  RPM BHP  RPM BHP  RPM BHP  RPM BHP
0.8
DO NOT
OPERATE
4602 884 2.13
1 4749 940 2.44 4180 885 1.89
1.2 4251 945 2.12 3642 896 1.58
1.4 4443 1001 2.5 3744 951 1.8
1.6 4587 1056 2.82 3971 1006 2.17
1.8 4760 1105 3.23 4071 1061 2.43 3342 1012 1.86
2 4364 1114 2.91 3579 1067 2.05
Notes :
Assume dry coil with lter in place; CFM correction for wet coil = 3%
Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Applications that exceed the above could
require a larger motor. Minimum rated SCFM is 350 per ton.